Table 1. Dimensions - Rack-mounted drawer
Measurements Width Depth Height EIA Units3 Weight
Metric 437 mm 731 mm 178 mm 4 44.7 kg
English 17.2 in. 28.8 in. 7.0 in. 98.5 lb
Table 2. Dimensions - stand-alone server
Measurements Width Depth Height Weight
Metric 201 mm 779 mm 533 mm 62 kg
English 7.9 in. 30.7 in. 21.0 in. 137 lb
Table 3. Shipping dimensions - Rack-mounted drawer
Measurements Width Depth Height Weight
Metric 648 mm 991 mm 704 mm 80 kg
English 25.5 in. 39 in. 27.7 in. 175 lb
Table 4. Shipping dimensions - Rack-mounted drawer (China)
Measurements Width Depth Height Weight
Metric 640 mm 965 mm 692 mm 80 kg
English 25.2 in. 38 in. 27.25 in. 1.75 lb
Table 5. Shipping dimensions - stand-alone server4
Measurements Width Depth Height Weight
Metric 648 mm 991 mm 704 mm 80 kg
English 25.5 in. 39 in. 27.7 in. 175 lb
Table 6. Shipping dimensions - stand-alone server (China)4
Measurements Width Depth Height Weight
Metric 640 mm 965 mm 692 mm 80 kg
English 25.2 in. 38 in. 27.25 in. 175 lb

Feature code for drawer mounted in rack

Power distribution Unit (PDU), 0551,7014-T00, 7014-T42 and 0553, and 0555 racks

0230 (9113-550), 7886 (9406-550)  
Table 7. Electrical
Electrical characteristics Properties
kVA (maximum) 1.158
Rated voltage, rated amps, and frequency6

9113-550, OpenPower™ 720, 9133-55A

One processor card installed

100 - 127 V ac (12 A) to 200-240 V ac (10 A) at 50 to 60 plus or minus 0.5 Hz

9133-55A, 9113-550

9406-550

OpenPower 720

Two processor cards installed

200 - 240 V ac (10 A) at 50 to 60 plus or minus 0.5 Hz

200 - 240 V ac (10 A) at 50 to 60 plus or minus 0.5 Hz

Thermal output (maximum) 3754 Btu/hr
Maximum power consumption 1100 W
Power factor 0.95
Inrush current (maximum) 85 A
Leakage current (maximum) 1.5 mA
Phase 1
Dual power feature code Included
Branch circuit breaker 20 A (maximum)
Table 8. Environment requirements
Environment Temperature
Recommended operating temperature2 5 - 35 °C (41 - 95 °F)
Nonoperating temperature 5 - 45 °C (41 - 113 °F)
Shipping temperature -40 - 60 °C (-40 - 140°F
Operating5 Nonoperating
Maximum dew point 28 °C (82.4 - °F) 29 °C (84.2 - °F)
Noncondensing humidity 8 - 80% 8 - 80%
Maximum altitude 3048 m (10 000 ft) 3048 m (10 000 ft)
Table 9. Noise emissions1, 10
Product description Declared A-weighted sound power level, LWad (B) Declared A-weighted sound pressure level, LpAm (dB)
Operating Idle Operating Idle
stand-alone models: 9406-550, 9113-550, OpenPower 720 with two hard drives and non-redundant power 6.0 5.9 42 41
Rack-mounted models:9406-550, 9113-550, OpenPower 720 with two hard drives and non-redundant power 6.1 6.0 44 43
Rack-mounted models:9406-550, 9113-550, OpenPower 720 with eight hard drives and redundant power 6.3 6.2 45 45
Rack-mounted model: 9133-55A with eight hard drives and redundant power 6.89 6.69    
Table 10. Service clearances
Clearances Front Back Left/right Top
Operating 762 mm (30 in.) 762 mm (30 in.)  
Nonoperating 762 mm (30 in.) 762 mm (30 in.) 762 mm (30 in.) 762 mm (30 in.)

Electromagnetic compatibility compliance: This server meets the following electromagnetic compatibility specifications: FCC (CFR 47, Part 15); VCCI; CISPR-22; 89/336/EEC; BSMI (A2/NZS 3548:1995); C-Tick; ICES/NMB-003; Korean EMI/EMC (MIC Notice 2000–94, Notice 2000–72); People's Republic of China Commodity Inspection Law

Safety compliance: This server is designed and certified to meet the following safety standards: UL 60950; CAN/CSA C22.2 No. 60950–00; EN 60950; IEC 60950 including all National Differences

Table 11. Notes
Notes:
  1. For a description of noise emission values, see Acoustics.
  2. Class 3 product as defined in ASHRAE Thermal Guidelines for Data Processing Environments. The allowable operating range is 5 - 35 °C (41 - 95 °F). See the Temperature and humidity design criteria topic for more information.
  3. See 0551, 0553, 0555, and 7014 rack configurations for typical configurations when the 0551, 0553, 0555 or 7014 rack is populated with various server models.
  4. stand-alone server is shipped on its side
  5. All Model 550 disk bays should be filled when the unit is shipped from IBM® with either disk drives or slot fillers, but if a disk is removed, refill the disk slot with either another disk drive or a disk slot filler. Filling the disk drive slot will help ensure proper airflow for cooling and help maintain optimal EMI compliance. Ordering feature 6598 results in four additional disk slot fillers being shipped.
  6. The power supplies automatically accept any voltage with the published rated voltage range for a defined processor configuration. If dual power supplies are installed and operating, the power supplies draw approximately equal current from the utility (mains) and provide approximately equal current to the load.
  7. Configured with two disk drives and non-redundant power system.
  8. Configured with eight disk drives and redundant power system.
  9. This is an estimated value.
  10. All measurements made in conformance with ISO 7779 and declared in conformance with ISO 9296.

Special Hardware Management Console considerations

When the 9406-550, 9113-550, OpenPower 720, 9133-55A servers are managed by a Hardware Management Console (HMC), the console must be provided within the same room and within 8 m (26 ft) of the server.

Note: As an alternative to the local HMC requirement, it is acceptable for you to provide a supported device, such as a PC, with connectivity and authority to operate through a remotely attached HMC. This local device must be in the same room and within 8 m (26 ft) of your server, and provide functional capability equivalent to the HMC that it replaces and that is needed by the service representative to service the system.