Hardware specifications provide detailed information for your rack, including dimensions, electrical, power, temperature, environment, and service clearances.
| Dimensions | Properties |
|---|---|
| Height | 2015 mm (79.3 in.) |
| Capacity | 42 usable EIA units |
| Height with PDP - DC only | Not applicable |
| Width without side panels | 623 mm (24.5 in.) |
| Width with side panels | 644 mm (25.4 in) |
| Depth with back door only | 1042 mm (41.0 in.) |
| Depth with back door and front door | 1098 mm (43.3 in.) |
| Depth with sculptured style front door | 1147 mm (45.2 in.) |
| Weight Base rack (empty) | 261 kg (575 lb) |
| Weight Full rack | 930 kg (2045 lb) See 7014-T00, 7014-T42 and 0553 rack weight distribution and floor loading |
| Weight Slim doors | 15.4 kg (34 lb) |
| Weight Side covers | 16.3 kg (36 lb) |
| Electrical characteristics | Properties |
|---|---|
| DC rack voltage (nominal) | -48 V dc |
| Power source loading maximum in kVa2 | See Power cord options for the 7014, 0551, 0553, and 0555 racks for details |
| Voltage range (V dc) | -40 - -60 |
| AC rack | 683 Btu/hr |
| Power source loading maximum in kVa (per PDB)3 | 135 W |
| Voltage range (V ac) | 200 - 240 |
| Frequency (Hz) | 50 or 60 |
| Front | Back | Sides |
|---|---|---|
| 915 mm (36 in.) | 915 mm (36 in.) | 915 mm (36 in.) |
See your server or hardware specifications for specific requirements.
See your server or hardware specifications for specific requirements.
Rack noise levels are a function of the number and type of drawers installed. See your server or hardware specifications for specific requirements3.
Rack airflow requirements are a function of the number and type of drawers installed4. Refer to the individual drawer specifications.
Note:
|
The following diagram provides the caster and leveler locations for the 7014-T00, 7014-T42, 0551, 0553, and 0555 racks.