POWER7 information

Replacing GX adapters in the 8202-E4B, 8202-E4C, 8202-E4D, 8205-E6B, 8205-E6C, or 8205-E6D

Learn how to replace GX adapters in the 8202-E4B, 8202-E4C, 8202-E4D, 8205-E6B, 8205-E6C, or 8205-E6D systems with the system power turned off.

If you are installing a new adapter, see Installing GX adapters in the 8202-E4B, 8202-E4C, 8202-E4D, 8205-E6B, 8205-E6C, or 8205-E6D to obtain adapter slot locations and required prerequisites. Complete this procedure if you are replacing the GX adapter in the system. You must have removed the failed GX adapter before you replace it with a new adapter. For instructions, see Removing GX adapters from the 8202-E4B, 8202-E4C, 8202-E4D, 8205-E6B, 8205-E6C, or 8205-E6D.

If your system is managed by the Hardware Management Console (HMC), use the HMC to replace an adapter. For instructions, see Exchanging a part by using the Hardware Management Console.

If your system is not managed by an HMC, complete the following steps to replace an adapter:

  1. Carefully grasp the new adapter assembly by the plastic latches and align the adapter assembly with the slot and its connector on the system backplane.
  2. Slowly slide the adapter along the glides until it stops.
    Attention: When you install an adapter into the system, be sure that it is completely and correctly seated in its connector.
  3. Evenly rotate the latches (A) into the locked position, as shown in Figure 1 and Figure 2.
  4. Rotate the latch (B) into the closed position to lock the adapter into the adapter slot.
    Figure 1. Installing the GX adapter in a rack-mounted 8202-E4B or 8205-E6B system
    Graphic showing installing the GX adapter in a rack-mounted system
    Figure 2. Installing the GX adapter (FC EJ03) in a rack-mounted 8202-E4C, 8202-E4D, 8205-E6C, or 8205-E6D system
    Graphic showing installing the GX adapter (FC EJ03) in a rack-mounted system
  5. Replace the service access cover:
  6. For a rack-mounted system, place the system in the operating position. For instructions, see Placing a rack-mounted 8202-E4B, 8202-E4C, 8202-E4D, 8205-E6B, 8205-E6C, or 8205-E6D system in the operating position.
  7. From the rear of the system, replace the adapter cables.
    Note: Mechanical brackets do not have to be removed and replaced when just replacing a GX adapter.
  8. If you are working on a rack-mounted system unit, ensure that the system cables are routed through the cable-management arm correctly.
  9. If you are installing the adapter as part of another procedure, return to that procedure now. If your service actions are complete, continue with the following steps:
    1. Reconnect the power source.
    2. Start the system. For instructions, see Starting the system or logical partition.
    3. Verify the installed part:
      • If you replaced the part because of a service action, verify the installed part. For instructions, see Verifying a repair.
      • If you installed the part for any other reason, verify the installed part. For instructions, see Verifying the installed part.