subscribe iconSubscribe to this information

Model 9118-575 server specifications

Server specifications provide detailed information for your server, including dimensions, electrical, power, temperature, environment, and service clearances.

The model 9118-575 refers to the complete system. The system consists of multiple components, as summarized in the following table.

Table 1. Model 9118-575 components
Model Description Minimum per system Maximum per system
FC5793 42 EIA unit, 24-inch rack (54-inch deep) 1 1
FC7945 Slimline door set for FC5793 rack (front and rear) 11 11
FC7947 Acoustic door set for FC5793 rack (front and rear) 11 11
9118-575 (FC7836)3 8-core, 1.9 GHz processor 1 12
9118-575 (FC7657)3 16-core, 1.5 GHz processor 1 12
9118-575 (FC7675)3 8-core, 2.2 GHz processor 1 12
9118-575 (FC7676)3 16-core, 1.9 GHz processor 1 12
Various Hardware Management Console (HMC)2 1 2
7045-SW4 HPS switch 0 2
FC5791 and FC5794 I/O drawer 0 5
FC6200 or FC6201 Optional integrated battery backup 0 6
Note:
  1. Either slimline doors or acoustical doors are selected during the order process. Slimline doors do not meet the acoustic limits for Category 1A or 1B.
  2. For model 9118-575, a Hardware Management Console must be provided within the same room and within 8 m (26 ft) of the server. Or, as an alternative to the local HMC requirement, it is acceptable for you to provide a supported device (such as, a PC), with connectivity and authority to operate through a remotely-attached HMC. This local device must be in the same room and within 8 m (26 ft) of your server, and provide functional capability equivalent to the HMC that it replaces and that is needed by the service representative to service the server.
  3. The maximum number of processors per system is the total number of FC7836, FC7657, FC7675, and FC7676 that can be combined to a maximum of 12.
Table 2. Dimensions and weight1
Physical Characteristic Slimline doors2 Acoustical doors2
Height 2025 mm (79.7 in.) 2025 mm (79.7 in.)
Width 785 mm (30.9 in.) 785 mm (30.9 in.)
Depth 1529 mm (60.2 in.) 1885 mm (74.2 in.)
Table 3. Weight - maximum configuration (with 1.9 GHz processor) Single frame
With integrated battery backup and slimline doors Without integrated battery backup with slimline doors With integrated battery backup and with acoustical doors Without integrated battery backup and with acoustical doors
1569 kg (3460 lb) 1439 kg (3173 lb) 1578 kg (3479 lb) 1448 kg (3192 lb)
Table 4. Shipping dimensions and weight
Dimensions Measurement
Height 2311 mm (91 in.)
Width 940 mm (37 in.)
Depth 1613 mm (63.5 in.)
Weight Varies by configuration
Table 5. Electrical and thermal characteristics (3-phase)
Rated voltage and frequency (three-phase) 200 - 240 V ac at 50 - 60 Hz 380 - 415 V ac at 50 - 60 Hz 480 V ac at 50 - 60 Hz
Rated current, power cord with 48A plug, FC 8688 or 8689 (amperes per phase) 48 -- --
Rated current, all other power cords (amps, per phase) 60 32 24
Maximum power 41.6 kW  
Power factor, typical 0.99 0.97 0.93
Inrush current (maximum)3 163 A  
Thermal output 142 kBtu/hr 142 kBtu/hr 142 kBtu/hr
Dual power feature code Standard7  
Branch circuit breaker and cord information See Breaker rating and cord information  
Table 6. Environment specifications (based on an altitude of 1295 m (4250 ft)
Environment Operating Nonoperating Storage4 Shipping4
Maximum wet bulb 23°C (73.4°F) 27°C (80.6°F) 29°C (84.2°F) 29°C (84.2°F)
Noncondensing relative humidity 8 - 80 % 8 - 80 % 5 - 80 % 5 - 100 %
Table 7. Environment temperatures (based on an altitude of 1295 m (4250 ft)
Environment Temperature
Recommended operating temperature8 10 - 32°C (50 - 89.6°F)
Nonoperating temperature 10 - 43°C (50 - 109.4°F)
Storage temperature 1 - 60°C (33.8 - 140°F)
Shipping temperature -40 - 60°C (-40 - 140°F)
Table 8. Declared acoustical noise emissions7
Product configuration Declared A-Weighted Sound Power Level, LWAd (Bels)5, 6 Declared A-Weighted Sound Pressure Level, LpAM (dB)5, 6 (bystander, 1 m)
  Operating Idle Operating Idle
Small configuration: Two processors, bulk power, and one I/O drawer; nominal conditions, slimline door set 8.2 8.2 65 65
Small configuration: Two processors, bulk power, and one I/O drawer; nominal conditions, acoustical door set 7.6 7.6 59 59
Typical configuration: six processors, bulk power, and one I/O drawer; nominal conditions, slimline door set 8.67 8.67 69 69
Typical configuration: six processors, bulk power, and one I/O drawer; nominal conditions, acoustical door set 7.9 7.9 62 62
Maximum configuration: 12 processors, bulk power, and two I/O drawers; nominal conditions, slimline door set 8.97 8.97 727 727
Maximum configuration: 12 processors, bulk power, and two I/O drawers; nominal conditions, acoustical door set 8.2 8.2 65 65

Electromagnetic compatibility compliance: This server meets the following electromagnetic compatibility specifications: FCC (CFR 47, Part 15); VCCI; CISPR-22; 89/336/EEC; BSMI (A2/NZS 3548:1995); C-Tick; ICES/NMB-003; Korean EMI/EMC (MIC Notice 2000–94, Notice 2000–72); People's Republic of China Commodity Inspection Law

Safety compliance: This server is designed and certified to meet the following safety standards: UL 60950-1; CAN/CSA C22.2 No. 60950-1; EN 60950-1; IEC 60950-1 including all national differences

Table 9. Notes
Notes:
  1. For configuration weights, see Approximate system weights by configuration
  2. Doors are not installed during product shipment to the customer.
  3. Inrush currents occur only at initial application of power (short duration for charging capacitors). No inrush currents occur during the normal power off-on cycle.
  4. When an IBM-approved vapor bag and desiccant packets are used to protect the system, the storage specifications are valid for 6 months and the shipping specifications are valid for 1 month. Otherwise, storage and shipping specifications are valid for two weeks each.
  5. LWAd is the upper-limit A-weighted sound level; LpAM is the mean A-weighted sound pressure measured at the 1-meter bystander postions; 1 B = 10 dB.
  6. All measurements made in conformance with ISO 7779 and declared in conformance with 9296.
  7. Attention: Your server installation might be subject to government regulations (such as those prescribed by OSHA or European Community Directives) that cover noise level exposure in the workplace. The model 9118-575 is available with an optional acoustical door feature that can reduce the likelihood of exceeding noise level exposure limits for densely populated racks. The actual sound pressure levels in your installation will depend on a variety of factors, including the number of racks in the installation; the size, materials, and configuration of the room where the racks are installed; the noise levels from other equipment; the room ambient temperature, and employees' location in relation to the equipment. It is recommended that a qualified person, such as an industrial hygienist or acoustical consultant, be consulted to determine whether the sound pressure levels to which employees might be exposed exceed regulatory limits.
  8. The upper limit of the dry bulb temperature must be derated 1°C (1.8 °F) per 219 m (719 ft) above 1295 m (4250 ft). Maximum altitude is 3048 m (10000 ft).