Server specifications provide detailed information for
your server, including dimensions, electrical, power, temperature,
environment, and service clearances.
Use the following specifications to plan for your server.
The 5074, 5078, or 5079
PCI expansion unit is available with model 9406-830 or model SB2.
Table 1. Dimensions| Measurements |
Width |
Depth |
Height |
Maximum configuration weight |
| Metric |
483 mm |
1080 mm |
1270 mm |
400 kg |
| English |
19.0 in. |
42.5 in. |
50.0 in. |
881.5 lb |
Table 2. Electrical| Electrical characteristics |
Property |
| kVA (maximum) |
1.684 |
| Rated voltage and frequency3 |
200-240 V ac at 50-60 plus or
minus 0.5 Hz |
| Thermal output (maximum) |
5461 Btu/hr |
| Power requirements (maximum) |
1600 W |
| Power factor |
0.95 |
| Inrush current |
80 A |
| Leakage current (maximum) |
3.5 mA |
| Phase |
1 |
Table 3. Temperature requirements| Operating |
Nonoperating |
| 10 - 38°C (50 - 100.4°F) |
1 - 60°C (33.8 - 140°F) |
Table 4. Environment requirements| Property |
Operating |
Nonoperating |
| Noncondensing humidity
|
8 - 80% |
8 - 80% |
| Wet bulb temperature
|
22.8°C (73°F) |
27°C (80.6°F) |
| Maximum altitude
|
3048 m (10 000 ft) |
|
Table 5. Noise emissions| Property |
Operating |
Idle |
| LWAd (Category
2D, General busness) |
6.7 bels |
6.7 bels |
| LpAm (1-meter
bystander) |
50 dB |
49 dB |
| For a
description of noise emission values, see Acoustics. |
Table 6. Service clearances| Front |
Back |
Sides1 |
Top1 |
| 762 mm |
762 mm |
762 mm |
762 mm |
| 30 in. |
30 in. |
30 in. |
30 in. |
| 1Side
and top clearances are optional when operating. |
Table 7. NotesNote: The power
supplies automatically accept any voltage with the published rated
voltage range. If dual power supplies are installed and operating,
the power supplies draw approximately equal current from the utility
(mains) and provide approximately equal current to the load.
|