Use the floor loading information to determine the floor
loading for various configurations.
The following figure shows the floor loading dimensions
for 6954 and 6953 expansion racks. Use this figure in conjunction
with the tables to determine the floor loading for various configurations.
Figure 1. Floor loading dimensions
The following tables show values for calculating floor loading
for the 6954 and 6953 expansion racks. Weights include acoustical
covers. Width and depth are indicated without covers.
Table 1. Powered I/O rack with eight
I/O drawers| Condition |
a (sides) |
b (front) |
c (back) |
Powered I/O rack |
| 1 |
25.4 mm (1 in.) |
254 mm (10 in.) |
254 mm (10 in.) |
206.0 lb/ft2 |
1006.0 kg/m2 |
| 2 |
25.4 mm (1 in.) |
508 mm (20 in.) |
508 mm (20 in.) |
165.8 lb/ft2 |
809.8 kg/m2 |
| 3 |
25.4 mm (1 in.) |
762 mm (30 in.) |
762 mm (30 in.) |
140.3 lb/ft2 |
684.8 kg/m2 |
| 4 |
254 mm (10 in.) |
254 mm (10 in.) |
254 mm (10 in.) |
140.2 lb/ft2 |
684.6 kg/m2 |
| 5 |
254 mm (10 in.) |
508 mm (20 in.) |
508 mm (20 in.) |
114.6 lb/ft2 |
559.7 kg/m2 |
| 6 |
254 mm (10 in.) |
762 mm (30 in.) |
762 mm (30 in.) |
98.3 lb/ft2 |
480.2 kg/m2 |
| 7 |
508 mm (20 in.) |
254 mm (10 in.) |
254 mm (10 in.) |
107.1 lb/ft2 |
522.7 kg/m2 |
| 8 |
508 mm (20 in.) |
508 mm (20 in.) |
508 mm (20 in.) |
88.8 lb/ft2 |
433.8 kg/m2 |
| 9 |
508 mm (20 in.) |
762 mm (30 in.) |
762 mm (30 in.) |
77.2 lb/ft2 |
377.1 kg/m2 |
| 10 |
762 mm (30 in.) |
254 mm (10 in.) |
254 mm (10 in.) |
88.7 lb/ft2 |
433.2 kg/m2 |
| 11 |
762 mm (30 in.) |
508 mm (20 in.) |
508 mm (20 in.) |
74.6 lb/ft2 |
364.1 kg/m2 |
| 12 |
762 mm (30 in.) |
762 mm (30 in.) |
762 mm (30 in.) |
65.6 lb/ft2 |
320.1 kg/m2 |
Table 2. Powered I/O
rack with four drawers| Condition |
a (sides) |
b (front) |
c (back) |
Powered I/O rack |
| 1 |
25.4 mm (1 in.) |
254 mm (10 in.) |
254 mm (10 in.) |
146.0 lb/ft2 |
713.0 kg/m2 |
| 2 |
25.4 mm (1 in.) |
508 mm (20 in.) |
508 mm (20 in.) |
119.2 lb/ft2 |
581.9 kg/m2 |
| 3 |
25.4 mm (1 in.) |
762 mm (30 in.) |
762 mm (30 in.) |
102.1 lb/ft2 |
498.3 kg/m2 |
| 4 |
254 mm (10 in.) |
254 mm (10 in.) |
254 mm (10 in.) |
102.0 lb/ft2 |
498.1 kg/m2 |
| 5 |
254 mm (10 in.) |
508 mm (20 in.) |
508 mm (20 in.) |
84.9 lb/ft2 |
414.7 kg/m2 |
| 6 |
254 mm (10 in.) |
762 mm (30 in.) |
762 mm (30 in.) |
74.0 lb/ft2 |
361.5 kg/m2 |
| 7 |
508 mm (20 in.) |
254 mm (10 in.) |
254 mm (10 in.) |
79.9 lb/ft2 |
389.9 kg/m2 |
| 8 |
508 mm (20 in.) |
508 mm (20 in.) |
508 mm (20 in.) |
67.7 lb/ft2 |
330.5 kg/m2 |
| 9 |
508 mm (20 in.) |
762 mm (30 in.) |
762 mm (30 in.) |
59.9 lb/ft2 |
292.6 kg/m2 |
| 10 |
762 mm (30 in.) |
254 mm (10 in.) |
254 mm (10 in.) |
67.6 lb/ft2 |
330.1 kg/m2 |
| 11 |
762 mm (30 in.) |
508 mm (20 in.) |
508 mm (20 in.) |
58.1 lb/ft2 |
283.9 kg/m2 |
| 12 |
762 mm (30 in.) |
762 mm (30 in.) |
762 mm (30 in.) |
52.1 lb/ft2 |
254.5 kg/m2 |
Table 3. Powered I/O
rack with seven drawers and an internal battery feature| Condition |
a (sides) |
b (front) |
c (back) |
Powered I/O rack |
| 1 |
25.4 mm (1 in.) |
254 mm (10 in.) |
254 mm (10 in.) |
221.6 lb/ft2 |
1081.8 kg/m2 |
| 2 |
25.4 mm (1 in.) |
508 mm (20 in.) |
508 mm (20 in.) |
177.9 lb/ft2 |
868.7 kg/m2 |
| 3 |
25.4 mm (1 in.) |
762 mm (30 in.) |
762 mm (30 in.) |
150.1 lb/ft2 |
733.1 kg/m2 |
| 4 |
254 mm (10 in.) |
254 mm (10 in.) |
254 mm (10 in.) |
150.1 lb/ft2 |
732.8 kg/m2 |
| 5 |
254 mm (10 in.) |
508 mm (20 in.) |
508 mm (20 in.) |
122.3 lb/ft2 |
597.2 kg/m2 |
| 6 |
254 mm (10 in.) |
762 mm (30 in.) |
762 mm (30 in.) |
104.6 lb/ft2 |
510.9 kg/m2 |
| 7 |
508 mm (20 in.) |
254 mm (10 in.) |
254 mm (10 in.) |
114.1 lb/ft2 |
557.0 kg/m2 |
| 8 |
508 mm (20 in.) |
508 mm (20 in.) |
508 mm (20 in.) |
94.3 lb/ft2 |
460.5 kg/m2 |
| 9 |
508 mm (20 in.) |
762 mm (30 in.) |
762 mm (30 in.) |
81.7 lb/ft2 |
399.0 kg/m2 |
| 10 |
762 mm (30 in.) |
254 mm (10 in.) |
254 mm (10 in.) |
94.2 lb/ft2 |
459.8 kg/m2 |
| 11 |
762 mm (30 in.) |
508 mm (20 in.) |
508 mm (20 in.) |
78.8 lb/ft2 |
384.9 kg/m2 |
| 12 |
762 mm (30 in.) |
762 mm (30 in.) |
762 mm (30 in.) |
69.0 lb/ft2 |
337.1 kg/m2 |
Table 4. Powered I/O
and expansion unit with 16 drawers| Condition |
a (sides) |
b (front) |
c (back) |
Powered I/O and
expansion unit |
| 1 |
25.4 mm (1 in.) |
254 mm (10 in.) |
254 mm (10 in.) |
192.9 lb/ft2 |
941.9 kg/m2 |
| 2 |
25.4 mm (1 in.) |
508 mm (20 in.) |
508 mm (20 in.) |
155.6 lb/ft2 |
759.9 kg/m2 |
| 3 |
25.4 mm (1 in.) |
762 mm (30 in.) |
762 mm (30 in.) |
131.9 lb/ft2 |
644.1 kg/m2 |
| 4 |
254 mm (10 in.) |
254 mm (10 in.) |
254 mm (10 in.) |
155.9 lb/ft2 |
761.3 kg/m2 |
| 5 |
254 mm (10 in.) |
508 mm (20 in.) |
508 mm (20 in.) |
126.9 lb/ft2 |
619.4 kg/m2 |
| 6 |
254 mm (10 in.) |
762 mm (30 in.) |
762 mm (30 in.) |
108.4 lb/ft2 |
529.1 kg/m2 |
| 7 |
508 mm (20 in.) |
254 mm (10 in.) |
254 mm (10 in.) |
130.2 lb/ft2 |
635.6 kg/m2 |
| 8 |
508 mm (20 in.) |
508 mm (20 in.) |
508 mm (20 in.) |
106.8 lb/ft2 |
521.6 kg/m2 |
| 9 |
508 mm (20 in.) |
762 mm (30 in.) |
762 mm (30 in.) |
92.0 lb/ft2 |
449.0 kg/m2 |
| 10 |
762 mm (30 in.) |
254 mm (10 in.) |
254 mm (10 in.) |
112.9 lb/ft2 |
551.2 kg/m2 |
| 11 |
762 mm (30 in.) |
508 mm (20 in.) |
508 mm (20 in.) |
93.4 lb/ft2 |
455.9 kg/m2 |
| 12 |
762 mm (30 in.) |
762 mm (30 in.) |
762 mm (30 in.) |
81.0 lb/ft2 |
395.3 kg/m2 |
Table 5. Powered I/O
and expansion unit with nine drawers| Condition |
a (sides) |
b (front) |
c (back) |
Powered I/O and
expansion unit |
| 1 |
25.4 mm (1 in.) |
254 mm (10 in.) |
254 mm (10 in.) |
142.6 lb/ft2 |
696.1 kg/m2 |
| 2 |
25.4 mm (1 in.) |
508 mm (20 in.) |
508 mm (20 in.) |
116.5 lb/ft2 |
568.7 kg/m2 |
| 3 |
25.4 mm (1 in.) |
762 mm (30 in.) |
762 mm (30 in.) |
99.9 lb/ft2 |
487.6 kg/m2 |
| 4 |
254 mm (10 in.) |
254 mm (10 in.) |
254 mm (10 in.) |
116.7 lb/ft2 |
569.7 kg/m2 |
| 5 |
254 mm (10 in.) |
508 mm (20 in.) |
508 mm (20 in.) |
96.3 lb/ft2 |
470.3 kg/m2 |
| 6 |
254 mm (10 in.) |
762 mm (30 in.) |
762 mm (30 in.) |
83.4 lb/ft2 |
407.0 kg/m2 |
| 7 |
508 mm (20 in.) |
254 mm (10 in.) |
254 mm (10 in.) |
98.6 lb/ft2 |
481.6 kg/m2 |
| 8 |
508 mm (20 in.) |
508 mm (20 in.) |
508 mm (20 in.) |
82.3 lb/ft2 |
401.8 kg/m2 |
| 9 |
508 mm (20 in.) |
762 mm (30 in.) |
762 mm (30 in.) |
71.9 lb/ft2 |
351.0 kg/m2 |
| 10 |
762 mm (30 in.) |
254 mm (10 in.) |
254 mm (10 in.) |
86.5 lb/ft2 |
422.5 kg/m2 |
| 11 |
762 mm (30 in.) |
508 mm (20 in.) |
508 mm (20 in.) |
72.9 lb/ft2 |
355.8 kg/m2n |
| 12 |
762 mm (30 in.) |
762 mm (30 in.) |
762 mm (30 in.) |
64.2 lb/ft2 |
313.4 kg/m2 |
Table 6. Powered I/O
and expansion unit with 15 drawers and an internal battery feature| Condition |
a (sides) |
b (front) |
c (back) |
Powered I/O and
expansion unit |
| 1 |
25.4 mm (1 in.) |
254 mm (10 in.) |
254 mm (10 in.) |
200.6 lb/ft2 |
979.6 kg/m2 |
| 2 |
25.4 mm (1 in.) |
508 mm (20 in.) |
508 mm (20 in.) |
161.6 lb/ft2 |
789.2 kg/m2 |
| 3 |
25.4 mm (1 in.) |
762 mm (30 in.) |
762 mm (30 in.) |
136.8 lb/ft2 |
668.0 kg/m2 |
| 4 |
254 mm (10 in.) |
254 mm (10 in.) |
254 mm (10 in.) |
161.9 lb/ft2 |
790.6 kg/m2 |
| 5 |
254 mm (10 in.) |
508 mm (20 in.) |
508 mm (20 in.) |
131.5 lb/ft2 |
642.2 kg/m2 |
| 6 |
254 mm (10 in.) |
762 mm (30 in.) |
762 mm (30 in.) |
112.2 lb/ft2 |
547.7 kg/m2 |
| 7 |
508 mm (20 in.) |
254 mm (10 in.) |
254 mm (10 in.) |
135.0 lb/ft2 |
659.2 kg/m2 |
| 8 |
508 mm (20 in.) |
508 mm (20 in.) |
508 mm (20 in.) |
110.6 lb/ft2 |
539.9 kg/m2 |
| 9 |
508 mm (20 in.) |
762 mm (30 in.) |
762 mm (30 in.) |
95.0 lb/ft2 |
464.0 kg/m2 |
| 10 |
762 mm (30 in.) |
254 mm (10 in.) |
254 mm (10 in.) |
116.9 lb/ft2 |
570.9 kg/m2 |
| 11 |
762 mm (30 in.) |
508 mm (20 in.) |
508 mm (20 in.) |
96.5 lb/ft2 |
471.3 kg/m2 |
| 12 |
762 mm (30 in.) |
762 mm (30 in.) |
762 mm (30 in.) |
83.5 lb/ft2 |
407.8 kg/m2 |
Table 7. Powered I/O
and expansion unit with eight drawers and an internal battery feature| Condition |
a (sides) |
b (front) |
c (back) |
Powered I/O and
expansion unit |
| 1 |
25.4 mm (1 in.) |
254 mm (10 in.) |
254 mm (10 in.) |
150.3 lb/ft2 |
733.8 kg/m2 |
| 2 |
25.4 mm (1 in.) |
508 mm (20 in.) |
508 mm (20 in.) |
122.5 lb/ft2 |
598.0 kg/m2 |
| 3 |
25.4 mm (1 in.) |
762 mm (30 in.) |
762 mm (30 in.) |
104.8 lb/ft2 |
511.5 kg/m2 |
| 4 |
254 mm (10 in.) |
254 mm (10 in.) |
254 mm (10 in.) |
122.7 lb/ft2 |
599.0 kg/m2 |
| 5 |
254 mm (10 in.) |
508 mm (20 in.) |
508 mm (20 in.) |
101.0 lb/ft2 |
493.1 kg/m2 |
| 6 |
254 mm (10 in.) |
762 mm (30 in.) |
762 mm (30 in.) |
87.2 lb/ft2 |
425.7 kg/m2 |
| 7 |
508 mm (20 in.) |
254 mm (10 in.) |
254 mm (10 in.) |
103.5 lb/ft2 |
505.2 kg/m2 |
| 8 |
508 mm (20 in.) |
508 mm (20 in.) |
508 mm (20 in.) |
86.1 lb/ft2 |
420.2 kg/m2 |
| 9 |
508 mm (20 in.) |
762 mm (30 in.) |
762 mm (30 in.) |
75.0 lb/ft2 |
366.0 kg/m2 |
| 10 |
762 mm (30 in.) |
254 mm (10 in.) |
254 mm (10 in.) |
90.6 lb/ft2 |
442.2 kg/m2 |
| 11 |
762 mm (30 in.) |
508 mm (20 in.) |
508 mm (20 in.) |
76.0 lb/ft2 |
371.2 kg/m2 |
| 12 |
762 mm (30 in.) |
762 mm (30 in.) |
762 mm (30 in.) |
66.8 lb/ft2 |
325.9 kg/m2 |