The system detected a room ambient over-temperature warning or
fault.
- Is the room ambient temperature within normal range (less than
35 degrees C or 95 degrees F)?
- No: Notify the customer. The customer must bring the room temperature
within normal range.
- Yes: Continue with the next step.
- Are the system front and rear doors free of obstructions?
- No: Notify the customer. The system must be free of obstructions
for proper air flow.
- Yes: Continue with the next step.
- Do all the positions in the processor subsystem contain processors
or fillers?
- Yes: Continue with the next step.
- No: Fill any open positions with processors or fillers. Then
go to Verifying the
repair. This ends the procedure.
- Do all the power supply positions contain power supplies or fillers?
- Yes: Continue with the next step.
- No: Fill any open positions with supplies or fan books. Then
go to Verifying the
repair. This ends the procedure.
- Are you working with reference code 7201?
- Yes: This ends the procedure.
- No: Continue with the next step.
- Are you working with reference code 7200?
- Yes: Refer to the reference code error log for failing rack/unit
location information, and then continue to next step. For information on displaying
error logs refer to Displaying error and event logs
- No: Continue with the next step.
- Perform the following:
- For models 285, 505, 51x, 52x, 55x, OpenPower® 710, OpenPower 720,
exchange the control panel (see CTLPNL).
Then continue with the next step.
- For models 561 and 570, exchange processor 1 and
processor 2, one at a time, until either the problem is resolved or you have
replaced both processors (see Finding
part locations). Then continue with the next step.
- After each FRU is exchanged, is the error code that sent you to
this procedure still reported?
- No: The problem has been corrected. Go to Verifying the repair. This ends
the procedure.
- Yes: Replace the next FRU on the list. If all FRUs on the list
have been replaced, call your next level of support. This ends the procedure.