AMBTEMP

The system detected a room ambient over-temperature warning or fault.

  1. Is the room ambient temperature within normal range (less than 35 degrees C or 95 degrees F)?
    • No: Notify the customer. The customer must bring the room temperature within normal range.
    • Yes: Continue with the next step.
  2. Are the system front and rear doors free of obstructions?
    • No: Notify the customer. The system must be free of obstructions for proper air flow.
    • Yes: Continue with the next step.
  3. Do all the positions in the processor subsystem contain processors or fillers?
    • Yes: Continue with the next step.
    • No: Fill any open positions with processors or fillers. Then go to Verifying the repair. This ends the procedure.
  4. Do all the power supply positions contain power supplies or fillers?
    • Yes: Continue with the next step.
    • No: Fill any open positions with supplies or fan books. Then go to Verifying the repair. This ends the procedure.
  5. Are you working with reference code 7201?
    • Yes: This ends the procedure.
    • No: Continue with the next step.
  6. Are you working with reference code 7200?
    • Yes: Refer to the reference code error log for failing rack/unit location information, and then continue to next step. For information on displaying error logs refer to Displaying error and event logs
    • No: Continue with the next step.
  7. Perform the following:
    • For models 285, 505, 51x, 52x, 55x, OpenPower® 710, OpenPower 720, exchange the control panel (see CTLPNL). Then continue with the next step.
    • For models 561 and 570, exchange processor 1 and processor 2, one at a time, until either the problem is resolved or you have replaced both processors (see Finding part locations). Then continue with the next step.
  8. After each FRU is exchanged, is the error code that sent you to this procedure still reported?
    • No: The problem has been corrected. Go to Verifying the repair. This ends the procedure.
    • Yes: Replace the next FRU on the list. If all FRUs on the list have been replaced, call your next level of support. This ends the procedure.