Model 8202-E4B, 8202-E4C, 8202-E4D, 8205-E6B, 8205-E6C, and 8205-E6D server specifications
Server specifications provide detailed information for your server, including dimensions, electrical, power, temperature, environment, and service clearances.

Use the following specifications to plan for your server.
| Width | Depth | Height | EIA units1 | Weight |
|---|---|---|---|---|
| 440 mm (17.3 in.) | 610 mm (24.0 in.) | 173 mm (6.8 in.) | 4 | 39.5 kg (87 lb ) |
| Width | Depth | Height | Weight |
|---|---|---|---|
328.5 mm (13 in.) (with tip foot) 183 mm (7.2 in.) (without tip foot) |
688 mm (27.0 in. ) | 541 mm (21.3 in.) | 50 kg (111 lb) |
| Width | Depth | Height | Weight1 |
|---|---|---|---|
| 610 mm (24 in.) | 711 mm (28 in.) | 1016 mm (40 in.) | 68 - 113 kg (150 - 250 lb) |
| 1This is an estimated value. | |||
| Width | Depth | Height | Weight1 |
|---|---|---|---|
| 660 mm (26 in.) | 737 mm (29 in.) | 1016 mm (40 in.) | 68 - 113 kg (150 - 250 lb) |
| 1This is an estimated value. | |||
| Width | Depth | Height | Weight1 |
|---|---|---|---|
| 660 mm (26 in.) | 622 mm (24.5 in.) | 1016 mm (40 in.) | 68 - 113 kg (150 - 250 lb) |
| 1This is an estimated value. | |||
| Electrical characteristics | Properties |
|---|---|
| Rated voltage and frequency1 | 100 - 127 V ac3 or 200 - 240 V ac at 47 - 63 Hz (8202-E4B, 8202-E4C, 8205-E6B, and 8205-E6C) |
| 100 - 127 V ac, 200 - 208 V ac, and 220 - 240 V ac (8202-E4D) | |
| 200 - 208 V ac and 220 - 240 V ac (8205-E6D) | |
| Thermal output (maximum)2 | 2560 Btu/hr (8202-E4B (Power 720 Express)) |
| 2867 Btu/hr (8202-E4C (Power 720 Express)) | |
| 3395 Btu/hr (8202-E4D (Power 720 Express)) | |
| 4778 Btu/hr (8205-E6B (Power 740 Express)) | |
| 5358 Btu/hr (8205-E6C (Power 740 Express)) | |
| 5562 Btu/hr (8205-E6D (Power 740 Express)) | |
| Maximum power consumption2 | 750 W (8202-E4B (Power 720 Express)) |
| 840 W (8202-E4C (Power 720 Express)) | |
| 995 W (8202-E4D (Power 720 Express)) | |
| 1400 W (8205-E6B (Power 740 Express)) | |
| 1570 W (8205-E6C (Power 740 Express)) | |
| 1630 W (8205-E6D (Power 740 Express)) | |
| Maximum kVA4 | 0.765 (8202-E4B (Power 720 Express)) |
| 0.857 (8202-E4C (Power 720 Express)) | |
| 1.015 (8202-E4D (Power 720 Express)) | |
| 1.429 (8205-E6B (Power 740 Express)) | |
| 1.602 (8205-E6C (Power 740 Express)) | |
| 1.664 (8205-E6D (Power 740 Express)) | |
| Power factor | 0.98 |
| Inrush current (maximum) | 85 A (8202-E4B, 8202-E4C, 8205-E6B, and 8205-E6C) |
| 12 A, 6 A, and 6 A (8202-E4D) | |
| 9 A and 9 A (8205-E6D) | |
| Leakage current (maximum) | 0.74 mA |
| Phase | Single |
| Dual power feature code | 2 x 5603 |
| Branch circuit breaker | 20 A maximum |
| Drawer mounted in 7014-T00 and 7014-T42 racks, and power distribution unit (PDU) |
0298 or 0299 |
Notes:
|
|
| Environment | Temperature |
|---|---|
| Recommended operating temperature | 18°C - 27°C (64°F - 80°F) |
| Allowable operating temperature | 5°C - 35°C (41°F - 95°F) (Models 8202-E4B, 8202-E4C, 8205-E6B, and 8205-E6C) |
| 5°C - 40°C (41°F - 104°F) (Models 8202-E4D and 8205-E6D) | |
| Nonoperating temperature | 5°C - 45°C (41°F - 113°F) |
| Recommended relative humidity range | 5.5°C (42°F) dew point to 60% RH and 15°C (59°F) dew point |
| Allowable relative humidity range | 20% - 80% |
| Nonoperating relative humidity range | 8% - 80% |
| Shipping temperature1 | -40°C to 60°C (-40°F to 140°F) |
| Shipping humidity range | 5% - 100% |
| Operating dew point | 28°C (84°F) |
| Altitude range | 0 - 3050 m (0 - 10000 ft)2 |
1 The maximum wet bulb temperature is 29°C (84°F). If one or more feature codes that are listed in Table 8 are installed, then the maximum wet bulb temperature is 28°C (82°F). 2 Derate maximum dry-bulb temperature 1°C/300 m above 900 m. |
|
| Feature codes (FCs) | Feature code names |
|---|---|
1738 / EQ38 |
856 GB (IBM i) 10K RPM SAS HDD (Gen2-S) |
1752 / EQ52 |
900 GB (AIX/Linux) 10K RPM SAS HDD (Gen2-S) |
1917 / 1866 |
146 GB (AIX/Linux) 15K RPM SAS HDD (Gen2-S) |
1925 / 1869 |
300 GB (AIX/Linux) 10K RPM SAS HDD (Gen2-S) |
1947 / 1868 |
139 GB (IBM i) 15K RPM SAS HDD (Gen2-S) |
1948 / 1927 |
283 GB (IBM i) 15K RPM SAS HDD (Gen2-S) |
1953 / 1929 |
300 GB (AIX/Linux) 15K RPM SAS HDD (Gen2-S) |
1956 / 1844 |
283 GB (IBM i) 10K RPM SAS HDD (Gen2-S) |
1962 / 1817 |
571 GB (IBM i) 10K RPM SAS HDD (Gen2-S) |
1964 / 1818 |
600 GB (AIX/Linux) 10K RPM SAS HDD (Gen2-S) |
ESD2 / EQD2 |
1.14 TB (IBM i) 10K RPM SAS HDD (Gen2-S) |
ESD3 / EQD3 |
1.2 TB (AIX/Linux) 10K RPM SAS HDD (Gen2-S) |
Note:
|
|
| Product description | Declared A-weighted sound power level, LWad (B) | Declared A-weighted sound pressure level, LpAm (dB) | ||
|---|---|---|---|---|
| Operating | Idle | Operating | Idle | |
| 8202-E4B, 8202-E4C, and 8202-E4D single-socket processor, rack-integrated configuration, 2 power supplies, 6 hard drives. | 5.6 | 5.5 | 40 | 38 |
| 8202-E4B, 8202-E4C, and 8202-E4D single-socket processor, 2 power supplies, 6 hard drives. Stand-alone system feature code (7572) | 5.6 | 5.5 | 39 | 37 |
| 8202-E4B, 8202-E4C, and 8202-E4D single-socket processor, rack-integrated configuration, 2 power supplies, low profile PCIe riser card, 6 hard drives | 6.3 | 6.3 | 47 | 47 |
| 8202-E4B, 8202-E4C, and 8202-E4D single-socket processor, rack-integrated configuration, 2 power supplies, 6 hard drives, and acoustic mode off | 6.5 | 6.5 | 49 | 49 |
| 8202-E4B, 8202-E4C, and 8202-E4D single-socket processor, rack-integrated configuration, 1 power supply, 6 hard drives | 6.5 | 6.5 | 51 | 51 |
| 8202-E4B, 8202-E4C, and 8202-E4D single-socket processor, rack-integrated configuration, 1 power supply, 6 hard drives, and low profile PCIe riser card. | 6.7 | 6.7 | 52 | 52 |
Notes:
|
||||
| Product description | Declared A-weighted sound power level, LWad (B) | Declared A-weighted sound pressure level, LpAm (dB) | ||
|---|---|---|---|---|
| Operating | Idle | Operating | Idle | |
| 8205-E6B, 8205-E6C, and 8205-E6D 2 socket processor, 2 power supplies, and IBM rack | 6.0 | 5.9 | 44 | 43 |
| 8205-E6B, 8205-E6C, and 8205-E6D 2 socket processor, 2 power supplies, IBM rack, and low-profile PCIe riser card | 6.1 | 6.1 | 42 | 42 |
| 8205-E6B, 8205-E6C, and 8205-E6D 2 socket processor, 2 power supplies, 8 hard drives, IBM rack, and acoustic mode off | 6.4 | 6.4 | 48 | 48 |
| 8205-E6B, 8205-E6C, and 8205-E6D 2 socket processor, 2 power supplies, 8 hard drives, IBM rack, acoustic mode off, and low-profile PCI riser card | 6.6 | 6.6 | 50 | 50 |
| 8205-E6B, 8205-E6C, and 8205-E6D 2 socket processor, 1 power supply, rack-integrated configuration, and low-profile PCI riser card | 6.7 | 6.7 | 52 | 52 |
| 8205-E6B, 8205-E6C, and 8205-E6D 2 socket processor, 8 hard drives, 2 power supplies, IBM rack, acoustic mode off, low-profile PCI riser card, and rack acoustical doors FC 6248 or 6249. | 6.1 | 6.1 | 42 | 42 |
Notes:
|
||||
| Clearances | Front | Back | Left or right | Top |
|---|---|---|---|---|
| Operating | 762 mm (30 in.) | 762 mm (30 in.) | ||
| Nonoperating | 762 mm (30 in.) | 762 mm (30 in.) | 762 mm (30 in.) | 762 mm (30 in.) |
Electromagnetic compatibility compliance: CISPR 22; CISPR 24; FCC, CFR 47, Part 15 (US); VCCI (Japan); Directive 2004/108/EC (EEA); ICES-003, Issue 4 (Canada); ACMA radio communications standard (Australia, New Zealand); CNS 13438 (Taiwan); Radio Waves Act, MIC Rule No. 210 (Korea); Commodity Inspection Law (China); TCVN 7189 (Vietnam); MoCI (Saudi Arabia); SI 961 (Israel); GOST R 51318.22, 51318.24 (Russia).
Safety compliance: IEC 60950; UL 60950; CSA 60950; EN 60950
Special Hardware Management Console considerations