Use the Breaker rating and cord information table to determine the circuit breaker rating for the power cords used with your server.
| 3-phase supply voltage (50/60 Hz) | 200 - 240 V ac | 200 - 240 V ac | 380 - 415 V ac | 480 V ac |
| Recommended customer-circuit-breaker rating1 | 60 A (60-A plug)or80 A (100-A plug) | 63 A (no plug) | 32 A (no plug) | 30 A(30A plug) |
| Cord information | 1.8 m (6 ft) and 4.3 m (14 ft) 6 AWG power cord (60-A plug), or 1.8 m (6 ft) and 4.3 m (14 ft) 6 AWG power cord (100-A Plug) | 14 foot, 6 AWG power cord, (electrician installed) | 14 foot, 8 AWG power cord, (electrician installed) | 6 and 14 foot, 8AWG power cord (30A plug) |
| Recommended receptacle | IEC 60309, 60 A, type 460R9W (not provided) or IEC 60309, 100A, type 4100R9W (not provided) | Not specified, electrician installed | Not specified, electrician installed | IEC 60309, 30 A, type 430R7W (not provided) |
| 1The exact circuit breaker ratings might not be available in all countries. Where the specified circuit breaker ratings are not acceptable, use the nearest available rating. Use of a time delayed circuit breaker is recommended. Use of a GFI circuit breaker is not recommended. 2When possible, use metal backbox with power cords using IEC 60309 plugs. |
||||