Server specifications provide detailed information for your server, including dimensions,
electrical, power, temperature, environment, and service clearances.
Use the following specifications to plan for your server.
Table 1. Dimensions for the 5105-22E, 9008-22L, 9009-22A,
9009-22G, 9223-22H, and 9223-22S1
| Width |
Depth |
Height |
EIA units |
Weight |
| 482 mm (18.97 in.) |
766.5 mm (30.2 in.) |
86.7 mm (3.4 in.) |
2 |
30.4 kg (67 lb) |
Note:
- The depth is measured from the front bezel to the back of the top cover. The depth from the
front rack EIA mounting post to the back of the server where the PCI cables exit is 713 mm (28
inches).
|
Table 2. Dimensions for the 9009-41A, 9009-41G,
9009-42A, 9009-42G, 9223-42H, and 9223-42S1
| Width |
Depth |
Height |
EIA units |
Weight |
| 482 mm (18.97 in.) |
769.6 mm (30.3 in.) |
173.3 mm (6.8 in.) |
4 |
36.3 kg (80 lb) (9009-41A and 9009-41G) |
| 39.9 kg (88 lb) (9009-42A, 9009-42G, 9223-42H, and
9223-42S) |
Note:
- The depth is measured from the front bezel to the back of the top cover. The depth from the
front rack EIA mounting post to the back of the server where the PCI cables exit is 713 mm (28
inches).
|
Table 3. Shipping dimensions for the 5105-22E, 9008-22L, 9009-22A,
9009-22G, 9223-22H, and 9223-22S (without pallet)
| Width |
Depth |
Height |
Weight |
| 991 mm (39 in.) |
597 mm (24 in.) |
261 mm (10.3 in.) |
45 kg (99 lb) |
Table 4. Shipping dimensions for the 9009-41A, 9009-41G,
9009-42A, 9009-42G, 9223-42H, and 9223-42S (without pallet)
| Width |
Depth |
Height |
Weight |
| 610 mm (24.0 in.) |
1016 mm (40.0 in.) |
345 mm (13.6 in.) |
53.7 kg (118.5 lb) |
Table 5. Pallet dimensions for the 5105-22E, 9008-22L, 9009-22A,
9009-22G, 9009-41A, 9009-41G, 9009-42A, 9009-42G,
9223-22H, 9223-22S, 9223-42H, and 9223-42S
| Width |
Depth |
Height |
Weight |
| 610 mm (24 in.) |
1016 mm (40 in.) |
125 mm (5 in.) |
10 kg (22 lb) |
Table 6. Electrical characteristics for the
9008-22L, 9009-22A, 9009-22G, 9009-41A, 9009-41G,
9009-42A, 9009-42G, 9223-22H, 9223-22S, 9223-42H, and
9223-42S
| Electrical characteristics |
Properties |
| AC rated voltage and frequency2 |
900 W PSU: 100 - 127 V ac or 200 - 240 V ac at 50 or 60 Hz plus or minus 3 Hz
(9009-41A and 9009-41G) |
| 1400 W PSU: 200 - 240 V ac at 50 or 60 Hz plus or minus 3 Hz (5105-22E, 9008-22L, 9009-22A,
9009-22G, 9009-42A, 9009-42G, 9223-22H, 9223-22S,
9223-42H, and 9223-42S) |
| Thermal output (maximum)3 |
6416 BTU/hr (9008-22L, 9009-22A, 9009-22G,
9223-22H, and 9223-22S) |
| 5461 BTU/hr (9009-41A and 9009-41G) |
| 9386 BTU/hr (9009-42A, 9009-42G, 9223-42H, and
9223-42S) |
| 2730 BTU/hr (5105-22E) |
| Maximum power consumption3 |
1880 W (9008-22L, 9009-22A, 9009-22G,
9223-22H, and 9223-22S) |
| 1600 W (9009-41A and 9009-41G) |
| 2750 W (9009-42A, 9009-42G, 9223-42H, and
9223-42S) |
| 800 W (5105-22E) |
| Maximum kVA4 |
1.94 kVA (9008-22L, 9009-22A, 9009-22G,
9223-22H, and 9223-22S) |
| 1.65 kVA (9009-41A and 9009-41G) |
| 2.835 kVA (9009-42A, 9009-42G, 9223-42H, and
9223-42S) |
| 0.816 kVA (5105-22E) |
| Phase |
Single |
Notes:
- Redundancy is supported. The 5105-22E, 9008-22L, 9009-22A,
9009-22G, 9223-22H, and 9223-22S have a maximum of two power supplies, but
can operate on one power supply. The 9009-41A, 9009-41G, 9009-42A,
9009-42G, 9223-42H, and 9223-42S have a maximum of four power supplies,
but can operate on two power supplies.
- The power supplies automatically accept any voltage with the published, rated-voltage range. If
multiple power supplies are installed and operating, the power supplies draw approximately equal
current from the utility (electrical supply) and provide approximately equal current to the
load.
- Power draw and heat load vary greatly
by configuration. When you plan for an electrical system, it is important to use the maximum values.
However, when you plan for heat load, you can use the IBM®
Systems Energy Estimator to obtain a heat output estimate based on a specific configuration. For
more information, see The IBM Systems Energy Estimator
website.
- To calculate the amperage, multiply the kVA by 1000 and divide that number by the operating
voltage.
|
Table 7. Environment
requirements
| Environment requirements |
| Environment (operating)1 |
| Properties |
Recommended |
Allowable2,3,4 |
| ASHRAE class |
|
A2 (Fourth edition) |
| Airflow direction |
Front-to-back |
| Temperature |
18.0°C – 27.0°C (64.4°F – 80.6°F) |
10.0°C – 35.0°C (50.0°F – 95.0°F) |
| Low end moisture |
-9.0°C (15.8°F) dew point |
-12.0°C (10.4°F) dew point and 8% relative humidity |
| High end moisture |
60% relative humidity and 15°C (59°F) dew point |
85% relative humidity and 21.0°C (69.8°F) dew point |
| Maximum altitude |
|
3050 m (10,000 ft) |
| Allowable environment
(nonoperating)5 |
| Temperature |
5°C - 45°C (41°F - 113°F) |
| Relative humidity |
8% to 85% |
| Maximum dew point |
27°C (80.6°F) |
| Environment (shipping) |
| Temperature |
-40.0°C to 60.0°C (-40°F to 140°F) |
| Relative humidity |
5% - 100% (no condensation) |
| Maximum wet bulb temperature |
29.0°C (84.2°F) |
| Environment (storage) |
| Temperature |
1°C - 60°C (33.8°F - 140°F) |
| Relative humidity |
5% - 80% (no condensation) |
| Maximum wet bulb temperature |
29°C (84.2°F) |
Notes:
- IBM provides the recommended operating environment as the
long-term operating environment that can result in the greatest reliability, energy efficiency, and
reliability. The allowable operating environment represents where the equipment is tested to verify
functionality. Due to the stresses that operating in the allowable envelope can place on the
equipment, these envelopes must be used for short-term operation, not continuous operation.
- Must derate the maximum allowable temperature 1°C (1.8°F) per 175 m (574 ft) above 900 m (2953
ft) up to a maximum allowable elevation of 3050 m (10000 ft).
- The minimum humidity level is the larger absolute humidity of the -12°C (10.4°F) dew point and
the 8% relative humidity. These levels intersect at approximately 25°C (77°F). Below this
intersection, the dew point (-12°C) represents the minimum moisture level, while above it, the
relative humidity (8%) is the minimum. For the upper moisture limit, the limit is the minimum
absolute humidity of the dew point and relative humidity that is stated.
- The following minimum requirements apply to data centers that are operated at low relative humidity:
- Data centers that have do not have ESD floors and where people are allowed to wear non-ESD shoes
might want to consider increasing humidity given that the risk of generating 8 kV increases slightly
at 8% relative humidity, when compared to 25% relative humidity.
- All mobile furnishings and equipment must be made of conductive or static dissipative materials
and be bonded to ground.
- During maintenance on any hardware, a properly functioning and grounded wrist strap must be used
by any personnel who comes in contact with information technology (IT) equipment.
- Equipment that is removed from the original shipping container and is installed, but is powered
down. The allowable non-operating environment is provided to define the environmental range that an
unpowered system can experience short term without being damaged.
|
Table 8. Noise emissions
for the 5105-22E, 9008-22L, 9009-22A,
9009-22G, 9223-22H, and 9223-22S
| Declared noise emission values in accordance with ISO 92961, 2,
3, 4, 5 |
| Production description |
Declared A-weighted sound power level, LWA,m (B) |
Declared A-weighted sound pressure level, LpA,m (dB) |
Statistical adder for verification, Kv (B) |
| |
Operating |
Idling |
Operating |
Idling |
Operating |
Idling |
|
5105-22E, 9008-22L, 9009-22A,
9009-22G, 9223-22H, and 9223-22S at 23°C (73.4°F) ambient temperature
|
6.5
|
6.4
|
52
|
52
|
0.3
|
0.3
|
|
5105-22E, 9008-22L, 9009-22A,
9009-22G, 9223-22H, and 9223-22S with PCIe adapters that require extra
cooling or at a temperature between 23°C - 27°C (73.4°F - 80.6°F).
|
7.46
|
7.46
|
61
|
61
|
0.3
|
0.3
|
|
5105-22E, 9008-22L, 9009-22A,
9009-22G, 9223-22H, and 9223-22S with acoustical doors (7042-T42
rack: (FCs EC07 and EC08) or 7965-S42 rack: (FCs ECRA and ECRB)) installed and with PCIe adapters
that require extra cooling or at a temperature between 23°C - 27°C (73.4°F - 80.6°F).
|
6.8
|
6.8
|
56
|
56
|
0.3
|
0.3
|
|
5105-22E, 9008-22L, 9009-22A,
9009-22G, 9223-22H, and 9223-22S at maximum allowable ambient operating
temperature.
|
8.36
|
8.36
|
70
|
70
|
0.3
|
0.3
|
Notes:
- Declared level LWA,m is the upper-limit A-weighted sound power level. Declared level
LPA,m is the mean A-weighted emission sound pressure level that is measured at the
1-meter bystander positions.
- The statistical adder for verification, Kv, is a quantity to be added to the declared
mean A-weighted sound power level, LWA,m, such that there is a 95% probability of
acceptance, when using the verification procedures of ISO 9296, if no more than 6.5% of the batch of
new equipment has A-weighted sound power levels greater than (LWA,m +
Kv).
- The quantity LWA,c (formerly called LWAd), can be computed from the sum of
LWA,m and Kv.
- All measurements made in conformance with ISO 7779 and declared in conformance with ISO
9296.
- 10 dB (decibel) equals 1 B (bel).
- Notice: Government regulations (such as those prescribed by OSHA or European Community
Directives) might govern noise level exposure in the workplace and might apply to you and your
server installation. This IBM system is available in racks
with optional acoustical door features that can help reduce the noise that is emitted from this
system. The actual sound pressure levels in your installation depend upon various factors, including
the number of racks in the installation; the size, materials, and configuration of the room where
you designate the racks to be installed; the noise levels from other equipment; the room ambient
temperature, and employees' location in relation to the equipment. Further, compliance with such
government regulations also depends upon various extra factors, including the duration of employees'
exposure and whether employees wear hearing protection. IBM
recommends that you consult with qualified experts in this field to determine whether you are in
compliance with the applicable regulations.
|
Table 9. Noise emissions
for the 9009-41A and 9009-41G
| Declared noise emission values in accordance with ISO 92961, 2,
3, 4, 5 |
| Production description |
Declared A-weighted sound power level, LWA,m (B) |
Declared A-weighted sound pressure level, LpA,m (dB) |
Statistical adder for verification, Kv (B) |
| |
Operating |
Idling |
Operating |
Idling |
Operating |
Idling |
|
9009-41A and 9009-41G (tower version (FC EJUB))
|
5.8
|
5.5
|
43
|
39
|
0.3
|
0.3
|
|
9009-41A and 9009-41G (rack version)
|
5.8
|
5.5
|
43
|
39
|
0.3
|
0.3
|
|
9009-41A and 9009-41G (rack and tower version) with NVMe U.2 drives or
high-power PCIe adapters.
|
7.3
|
7.3
|
60
|
60
|
0.3
|
0.3
|
|
9009-41A and 9009-41G (rack version) with high-power PCIe adapters and
acoustical doors (7042-T42 rack: (FCs EC07 and EC08) or 7965-S42 rack: (FCs ECRA and ECRB))
installed.
|
6.6
|
6.6
|
54
|
54
|
0.3
|
0.3
|
|
9009-41A and 9009-41G (rack and tower version) at maximum allowable ambient
operating temperature.
|
8.06
|
8.06
|
67
|
67
|
0.3
|
0.3
|
Notes:
- Declared level LWA,m is the upper-limit A-weighted sound power level. Declared level
LPA,m is the mean A-weighted emission sound pressure level that is measured at the
1-meter bystander positions.
- The statistical adder for verification, Kv, is a quantity to be added to the declared
mean A-weighted sound power level, LWA,m, such that there is a 95% probability of
acceptance, when using the verification procedures of ISO 9296, if no more than 6.5% of the batch of
new equipment has A-weighted sound power levels greater than (LWA,m +
Kv).
- The quantity LWA,c (formerly called LWAd), can be computed from the sum of
LWA,m and Kv.
- All measurements made in conformance with ISO 7779 and declared in conformance with ISO
9296.
- 10 dB (decibel) equals 1 B (bel).
- Notice: Government regulations (such as those prescribed by OSHA or European Community
Directives) might govern noise level exposure in the workplace and might apply to you and your
server installation. This IBM system is available in racks
with optional acoustical door features that can help reduce the noise that is emitted from this
system. The actual sound pressure levels in your installation depend upon various factors, including
the number of racks in the installation; the size, materials, and configuration of the room where
you designate the racks to be installed; the noise levels from other equipment; the room ambient
temperature, and employees' location in relation to the equipment. Further, compliance with such
government regulations also depends upon various extra factors, including the duration of employees'
exposure and whether employees wear hearing protection. IBM
recommends that you consult with qualified experts in this field to determine whether you are in
compliance with the applicable regulations.
|
Table 10. Noise emissions
for the 9009-42A, 9009-42G, 9223-42H, and
9223-42S
| Declared noise emission values in accordance with ISO 92961, 2,
3, 4, 5 |
| Production description |
Declared A-weighted sound power level, LWA,m (B) |
Declared A-weighted sound pressure level, LpA,m (dB) |
Statistical adder for verification, Kv (B) |
| |
Operating |
Idling |
Operating |
Idling |
Operating |
Idling |
|
9009-42A, 9009-42G, 9223-42H, and
9223-42S
|
6.6
|
6.5
|
53
|
53
|
0.3
|
0.3
|
|
9009-42A, 9009-42G, 9223-42H, and
9223-42S with high-power PCIe adapters.
|
7.46
|
7.46
|
61
|
61
|
0.3
|
0.3
|
|
9009-42A, 9009-42G, 9223-42H, and
9223-42S with high-power PCIe adapters and acoustical
doors (7042-T42 rack: (FCs EC07 and EC08) or 7965-S42 rack: (FCs ECRA and ECRB)) installed.
|
6.9
|
6.9
|
55
|
55
|
0.3
|
0.3
|
|
9009-42A, 9009-42G, 9223-42H, and
9223-42S at maximum allowable ambient operating
temperature.
|
8.16
|
8.16
|
68
|
68
|
0.3
|
0.3
|
Notes:
- Declared level LWA,m is the upper-limit A-weighted sound power level. Declared level
LPA,m is the mean A-weighted emission sound pressure level that is measured at the
1-meter bystander positions.
- The statistical adder for verification, Kv, is a quantity to be added to the declared
mean A-weighted sound power level, LWA,m, such that there is a 95% probability of
acceptance, when using the verification procedures of ISO 9296, if no more than 6.5% of the batch of
new equipment has A-weighted sound power levels greater than (LWA,m +
Kv).
- The quantity LWA,c (formerly called LWAd), can be computed from the sum of
LWA,m and Kv.
- All measurements made in conformance with ISO 7779 and declared in conformance with ISO
9296.
- 10 dB (decibel) equals 1 B (bel).
- Notice: Government regulations (such as those prescribed by OSHA or European Community
Directives) might govern noise level exposure in the workplace and might apply to you and your
server installation. This IBM system is available in racks
with optional acoustical door features that can help reduce the noise that is emitted from this
system. The actual sound pressure levels in your installation depend upon various factors, including
the number of racks in the installation; the size, materials, and configuration of the room where
you designate the racks to be installed; the noise levels from other equipment; the room ambient
temperature, and employees' location in relation to the equipment. Further, compliance with such
government regulations also depends upon various extra factors, including the duration of employees'
exposure and whether employees wear hearing protection. IBM
recommends that you consult with qualified experts in this field to determine whether you are in
compliance with the applicable regulations.
|
Table 11. Service clearances
| Clearances |
Front |
Rear |
Side1 |
Top1
|
| Operating |
762 mm (30 in.) |
762 mm (30 in.) |
|
|
| Nonoperating |
762 mm (30 in.) |
762 mm (30 in.) |
762 mm (30 in.) |
762 mm (30 in.) |
|
1 Side and top clearances are optional during operation.
|
Electromagnetic compatibility compliance: CISPR 22; CISPR 32;
CISPR 24; FCC, CFR 47, Part 15 (US); VCCI (Japan); Directive 2014/30/EU (EEA); ICES-003, Issue 6
(Canada); ACMA (Australia, New Zealand); CNS 13438 (Taiwan); Radio Waves Act (Korea); Commodity
Inspection Law (China); TCVN 7189 (Vietnam); MoCI (Saudi Arabia); SI 961 (Israel); EAC (EAEU)
Safety compliance: UL 60950-1:2007 Underwriters Laboratory; CAN/CSA22.2 No.
60950-1-07; EN60950-1:2006 + Am1 + Am2 European Norm; IEC 60950-1 2nd Edition + Am1 + Am2 and all
National Differences
Special Hardware Management Console considerations
When the server is managed by an HMC, the console must be provided within the same room and
within 8 m (26 ft) of the server. For more considerations, see Installing and configuring
the HMC.
Note: As an alternative to the local HMC requirement, you can provide a supported device, such as a
PC, with connectivity and authority to operate through a remotely attached HMC. This local device
must be in the same room and within 8 m (26 ft) of your server. This local device must provide
functional capabilities that are equivalent to the HMC that it replaces. This local device is needed
by the service representative to service the system.