POWER7 information

Model 8412-EAD, 9117-MMB, 9117-MMC, 9117-MMD, 9179-MHB, 9179-MHC, and 9179-MHD server specifications

Server specifications provide detailed information for IBM® Power® ESE (8412-EAD), IBM Power 770 (9117-MMB, 9117-MMC, 9117-MMD), and IBM Power 780 (9179-MHB, 9179-MHC, and 9179-MHD) servers including dimensions, electrical data, power, temperature, environment requirements, and service clearances.

Dimensions

Table 1. Server dimensions
Width Depth Height EIA units Weight Shipping weight (including packaging)
483 mm (19.0 in.) 863 mm (34.0 in.) 174 mm (6.9 in.) 4 EIA units 70.3 kg (155 lb) 93.5 - 95.5 kg (206.1 - 210.5 lb)
Table 2. Shipping dimensions for the 9117-MMD (including pallet)
Width Depth Height Weight (including packaging)
665 mm (26.2 in.) 1120 mm (44.1 in.) 174 mm (18.7 in.) 93.5 - 95.5 kg (206.1 - 210.5 lb)

Electrical

Table 3. Electrical
Electrical characteristics Properties
Voltage 200 - 240 V ac
Frequency 50 or 60 Hz (plus or minus 3 Hz)
Maximum thermal output 5461 Btu/hr per enclosure (Models 8412-EAD, 9117-MMB, 9117-MMC, 9117-MMD, and 9179-MHB)
6485 Btu/hr per enclosure (Models 9179-MHC and 9179-MHD)
Maximum power consumption 1600 watts per enclosure (Models 8412-EAD, 9117-MMB, 9117-MMC, 9117-MMD, and 9179-MHB)
1900 watts per enclosure (Models 9179-MHC and 9179-MHD)
Power factor .97
Maximum inrush current   95 amps
Phase   Single
Power source loading 1.649 kVA per enclosure (Models 8412-EAD, 9117-MMB, 9117-MMC, 9117-MMD, and 9179-MHB)
1.959 kVA per enclosure (Models 9179-MHC and 9179-MHD)
Notes:
  1. The power supplies automatically accept any voltage with the published, rated-voltage range. If dual power supplies are installed and operating, the power supplies draw approximately equal current from the utility (mains) and provide approximately equal current to the load.
  2. Maximum power consumption is specified for each 9117-MMB 16-core drawer. The 32-core, 48-core, and 64-core configurations are based on the use of multiple 16-core drawers (for example, a 32-core configuration consists of two 16-core drawers, and other configurations).
  3. Power draw and heat load vary greatly by configuration. When you plan for an electrical system, it is important to use maximum values. However, when you are planning for heat load, you can use the IBM® Systems Energy Estimator to obtain a heat output estimate based on a specific configuration. For more information, see The IBM Systems Energy Estimator website.
  4. Measured according to IEC 60950.
  5. To calculate the amperage, multiply the kVA by 1000 and divide that number by the operating voltage.

Environment requirements

Table 4. Environment requirements
Environment Recommended operating Allowable operating Nonoperating
Temperature1 18°C - 27°C (64°F - 80°F)

5°C - 35°C (41°F - 95°F) (Models 9117-MMB, 9117-MMC, 9179-MHC, and 9179-MHB)

5°C - 40°C (41°F - 104°F) (Models 8412-EAD, 9117-MMD, and 9179-MHD)

5°C - 45°C (41°F - 113°F)
Relative humidity (RH) 5.5°C (42°F) dew point to 60% RH and 15°C (59°F) dew point 20% - 80% 8% - 80%
Maximum operating altitude   3048 m (10 000 ft)  
Shipping temperature2     -40°C to 60°C (-40°F to 140°F)
Shipping relative humidity     5% - 100%
Dew point    29°C (84°F) 28°C (82°F) 

1 Derate maximum dry-bulb temperature 1°C/300 m above 900 m.

2 The maximum wet bulb temperature is 29°C (84°F). If one or more feature codes that are listed in Table 5 are installed, then the maximum wet bulb temperature is 28°C (82°F).

Table 5. Supported feature codes that affect environmental requirements1
Feature codes (FCs) Feature code names

1738 / EQ38

856 GB (IBM i) 10K RPM SAS HDD (Gen2-S)

1752 / EQ52

900 GB (AIX/Linux) 10K RPM SAS HDD (Gen2-S)

1917 / 1866

146 GB (AIX/Linux) 15K RPM SAS HDD (Gen2-S)

1925 / 1869

300 GB (AIX/Linux) 10K RPM SAS HDD (Gen2-S)

1947 / 1868

139 GB (IBM i) 15K RPM SAS HDD (Gen2-S)

1948 / 1927

283 GB (IBM i) 15K RPM SAS HDD (Gen2-S)

1953 / 1929

300 GB (AIX/Linux) 15K RPM SAS HDD (Gen2-S)

1956 / 1844

283 GB (IBM i) 10K RPM SAS HDD (Gen2-S)

1962 / 1817

571 GB (IBM i) 10K RPM SAS HDD (Gen2-S)

1964 / 1818

600 GB (AIX/Linux) 10K RPM SAS HDD (Gen2-S)

ESD2 / EQD2

1.14 TB (IBM i) 10K RPM SAS HDD (Gen2-S)

ESD3 / EQD3

1.2 TB (AIX/Linux) 10K RPM SAS HDD (Gen2-S)

Note:
  1. Any feature code that is listed in this table and is installed in your system decreases the maximum wet bulb temperature that is allowed during shipping from 29°C (84°F) to 28°C (82°F).
Table 6. Noise emissions
Product description Declared A-weighted sound power level, LwAqd (B) Declared A-weighted sound pressure level, LpAm (dB)
  Operating Idle Operating Idle
Model 9117-MMB and 9179-MHB single drawer (16 way) (2 socket- 8 core/socket) 6.8 6.8 51 51
Model 9117-MMB and 9179-MHB single drawer (16 way) (2 socket- 8 core/socket) with acoustical rack doors feature code 6248 or 6249 6.3 6.3 46 46
Model 9117-MMB and 9179-MHB four drawer (64 way) (8 socket- 8 core/socket) 7.3 7.3 54 54
Model 9117-MMB and 9179-MHB four drawer (64 way) (8 socket- 8 core/socket) with acoustical rack doors feature code 6248 or 6249 6.8 6.8 49 49
Model 8412-EAD, 9117-MMC, 9117-MMD, 9179-MHC, and 9179-MHD single drawer 24 active cores 7.1 7.1 55 55
Model 8412-EAD, 9117-MMC, 9117-MMD, 9179-MHC, and 9179-MHD single drawer 24 active cores with acoustic rack doors feature code 6248 or 6249 6.6 6.6 49 49
Model 8412-EAD, 9117-MMC, 9117-MMD, 9179-MHC, and 9179-MHD four drawers 96 active cores 7.6 7.6 60 60
Model 8412-EAD, 9117-MMC, 9117-MMD, 9179-MHC, and 9179-MHD four drawers 96 active cores with acoustic rack doors feature code 6248 or 6249 7.1 7.1 54 54
Notes:
  1. LwAd is the statistical upper limit of the A-weighted sound power level (rounded to the nearest 0.1).
  2. LpAm is the mean A-weighted emission sound pressure level that is measured at the 1-meter bystander position (rounded to the nearest dB).
  3. 10 dB (decibel) equals 1 B (bel).
  4. All measurements made in conformance with ISO 7779 and declared in conformance with ISO 9296.

Electromagnetic compatibility compliance

Electromagnetic compatibility compliance: FCC Part 15, ICES-003

Safety compliance

Safety compliance: IEC 60950; UL 60950; CSA 60950

Special Hardware Management Console considerations

The Hardware Management Console (HMC) must be provided within the same room and within 8 m (26 ft) of the server. For additional considerations, see Planning for HMC installation and configuration.

Note: As an alternative to the local HMC requirement, it is acceptable for you to provide a supported device, such as a computer, with connectivity and authority to operate through a remotely attached HMC. This local device must be in the same room and within 8 m (26 ft.) of your server, and provide functional capability equivalent to the HMC that it replaces and that is needed by the service representative to service the system.

Delivery and subsequent transportation of the equipment

DANGER
Heavy equipment—personal injury or equipment damage might result if mishandled. (D006)

You must prepare your environment, with assistance from an authorized service provider, to accept the new product based on the installation planning information provided. In anticipation of the equipment delivery, prepare the final installation site in advance so that professional movers or riggers can transport the equipment to the final installation site within the computer room. If, for some reason, this is not possible at the time of delivery, you must make arrangements to have professional movers or riggers return to finish the transportation at a later date. Only professional movers or riggers should transport the equipment. The authorized service provider can only perform minimal frame repositioning within the computer room, as needed, to perform required service actions. You are also responsible for using professional movers or riggers when you relocate or dispose of equipment.