TS7770 specifications and requirements
The following specifications and requirements are specific to the TS7770 and its components.
The 3952 Tape Frame (3952 F06 or F07) houses the components of the TS7770.
- TS7770 Server (3957-VED) (includes control unit and 2 I/O drawers)
- TS7770 Cache Controller (3956-CSB)
- TS7770 Cache Drawer(s) (3956-XSB) Internal power distribution units
- TS7770 Cache Controllers (3956-CSB)
- TS7770 Cache Drawer(s) (3956-XSB)
Base Frame | Expansion Frame, each (up to 2) | Client Rack Mount (min config/ max config) | |
---|---|---|---|
Width | 616 mm (24.25 in.) | 616 mm (24.25 in.) | 483 mm (19.0 in.) of each component |
Depth | 1425 mm (56.1 in.) | 1425 mm (56.1 in.) | Depth of the deepest component3757-VED (p9 pSeries) from front to back of the cable management arm & cables in the arm 38.9 inches (98.8 cm) |
Height | 1930.4 mm (76 in.) | 1930.4 mm (76 in.) |
2 disk module config 18U in height = Min config 4 disk module config 22U in height 6 disk module config 26U in height 8 disk module config 30U in height 10 disk module config 34U in height = Max config |
Weight | max 735.3 Kg (1,621 lib) | max 929.3 Kg (2,049 lbs) |
Min weight of components for configuration with 2 disk cache drawers is 243 kg (536.4 lbs) Max weight of components for configuration with 10 disk cache drawers is 456 kg (1,006 lbs) |
Power consumption | max 3480 watts | max 4400 watts | max 3480 watts |
Power phase options | single phase (240 V AC) or three phase (400 V AC) | single phase only (240 V AC) | |
Power frequency | 50 Hz - 60 Hz (+/- 3 Hz) | ||
Dry bulb temperature (recommended operating range) | 20°C to 25°C (68°F to 77°F) | ||
Relative humidity (recommended operating range) | 40 % to 55% |
If FC 7338, TS7700 Encryption-capable expansion frame is installed the TS7770 Storage Expansion Frame has these physical specifications when fully configured:The distance between a TS7770 Storage Expansion Frame and the TS7770 Base Frame cannot exceed 10 meters. This distance permits connection of the frames by using a 30-meter cable.
dd | Base Frame | Expansion Frame, each (up to 2) | Client Rack Mount (min config/ max config) |
---|---|---|---|
Width | 616 mm (24.25 in.) | 616 mm (24.25 in.) | 483 mm (19.0 in.) of each component |
Width | 616 mm (24.25 in.) | 616 mm (24.25 in.) | 483 mm (19.0 in.) of each component |
Depth | 1425 mm (56.1 in.) | 1425 mm (56.1 in.) | Depth of the deepest component3757-VED (p9 pSeries) from front to back of the cable management arm & cables in the arm 38.9 inches (98.8 cm) |
Height | 1930.4 mm (76 in.) | 1930.4 mm (76 in.) |
2 disk module config 18U in height = Min config 4 disk module config 22U in height 6 disk module config 26U in height 8 disk module config 30U in height 10 disk module config 34U in height = Max config |
Weight | max 735.3 Kg (1,621 lib) | max 929.3 Kg (2,049 lbs) |
Min weight of components for configuration with 2 disk cache drawers is 243 kg (536.4 lbs) Max weight of components for configuration with 10 disk cache drawers is 456 kg (1,006 lbs) |
Power consumption | max 3480 watts | max 4400 watts | max 3480 watts |
Power phase options | single phase (240 V AC) or three phase (400 V AC) | single phase only (240 V AC) | |
Power frequency | 50 Hz - 60 Hz (+/- 3 Hz) | ||
Dry bulb temperature (recommended operating range) | 20°C to 25°C (68°F to 77°F) | ||
Relative humidity (recommended operating range) | 40 % to 55% |
Component | Quantity of each component in 3952 Tape Frame as TS7770 Base frame | Quantity of each component in 3952 Tape Frame as optional TS7770 Storage Expansion Frame | |
---|---|---|---|
TS7770 Server (3957-VED) | 1 | 0 | |
TS7770 Cache Controller (3956-CSB) | 1 | 2 | |
TS7770 Cache Drawers (3956-XSB) | 9 | 18 | |
Component | Quantity of each component in 3952 Tape Frame as TS7770 Base frame | Quantity of each component in 3952 Tape Frame as optional TS7770 Storage Expansion Frame with FC 9336 1st Expansion Frame | Quantity of each component in 3952 Tape Frame as optional TS7770 Storage Expansion Frame with FC 9337 2nd Expansion Frame |
TS7770 Server (3957-VED) | 1 | 0 | 0 |
TS7770 Cache Controller (3956-CSB) | 1 | 2 | 2 |
TS7770 Cache Drawers (3956-XSB) | 9 | 18 | 18 |
Specification | TS7770 Server | TS7770 Cache Subsystem | ||
---|---|---|---|---|
Type and Model | 3957-VED | I/O expansion drawer (each of 2) |
TS7770 cache controller 3956-CSB | TS7770 cache expansion drawer 3956-XSB |
Width | 482 mm (18.97 in) | 440 mm (17.32 in.) Total width of two joined drawers |
483 mm (19.0 in) | 483 mm (19.0 in) |
Depth | 766.5 mm (30.2 in) | 800 mm (31.5 in.) | 556 mm (21.9 in) | 556 mm (21.9 in) |
Height | 86.7 mm (3.4 in) | 220 mm (8.66 in.) | 87 mm (3.4 in) | 87 mm (3.4 in) |
Weight | 30.4 kg (67 lbs) | 42.2 kg (92.8 lb.) weight of two combined Reflects weight of each, without cassettes |
27.7 kg (61.0 lb) fully configured | 26.7 kg (58.7 lb) fully configured |
Power | 180-240 V AC 50/60 Hz (+/- 3 Hz) |
180-240 V AC 50/60 Hz |
198-264 RMS† V AC 50/60 Hz |
198-264 RMS† V AC 50/60 Hz |
Unit height | 2 U | 5 U | 2 U | 2 U |
Temperature (non-operating) | 5-45 degrees C (41-113 degrees F) | Included in 3952 Tape Frame maximum | −10-65 degrees C (14-149 F) | 5-45 degrees C (41-113 F) |
Temperature (operating) | 5-40 degrees C (41-104 degrees F) Temperature depends on altitude, see Table 5. Suggested: 18-27 degrees C (64-80 degrees F) |
Included in 3952 Tape Frame maximum | 10-32 degrees C (50-89.6 F) | 10-32 degrees C (50-89.6 F) |
Relative humidity | Non-operating: 8-85% Operating: 20-60% |
Included in 3952 Tape Frame maximum | Non-operating: 8-80% Operating: 20%-80% |
Non-operating: 8-80% Operating: 20%-80% |
Maximum wet bulb (power off) | Non-operating: 28 degrees C (82 degrees F) |
Included in 3952 Tape Frame maximum | 23 degrees C (73.4 F) | 23 degrees C (73.4 F) |
Power consumption | 1400 watts (2X) max. | Included in 3952 Tape Frame maximum | 810 watts | 540 watts |
Thermal output | 6416 Btu/hour (max.) | Included in 3952 Tape Frame maximum | 2730 Btu/hr | 1820 Btu/hr |
Power-source loading | 1.6 kVA (max. config.) 3,048 m (10,000 ft.) max. altitude |
Included in 3952 Tape Frame maximum | 0.9 kVA | 0.6 kVA |
† Root Mean Square. In a multi-drawer configuration, total power is predicted to be a root mean square of the individual drawer maximums. |
Temperature (operating) | Altitude |
---|---|
5-40 degrees C (41-104 degrees F) Note: The minimum operating temperature cannot
go below 5 C (41 degrees F).
|
Up to 3050 meter @ 5-28 C (41-82 degrees F) |
Up to 2875 meter @ 29 C (84 degrees F) | |
Up to 2700 meter @ 30 C (86 degrees F) | |
Up to 2525 meter @ 31 C (88 degrees F) | |
Up to 2350 meter @ 32 C (89 degrees F) | |
Up to 2175 meter @ 33 C (91 degrees F) | |
Up to 2000 meter @ 34 C (93 degrees F) | |
Up to 1825 meter @ 35 C (95 degrees F) | |
Up to 1650 meter @ 36 C (96 degrees F) | |
Up to 1475 meter @ 37 C (98 degrees F) | |
Up to 1300 meter @ 38 C (100 degrees F) | |
Up to 1125 meter @ 39 C (102 degrees F) | |
Up to 950 meter @ 40 C (104 degrees F) |
TS7770 Base Frame power requirements
Your facility must ensure an available power supply to meet the input voltage requirements for the TS7770 Base Frame. Table 6 displays the maximum input power for a fully configured TS7770.
Power requirement | Value |
---|---|
Voltage | 200-240 V AC (single phase) |
Frequency | 50-60 Hz (+/- 3 Hz) |
Current | 24 amp |
Inrush current | 250 amp |
Power (watt) | 3480 watts |
Input power required | 4.8 kVA (single phase) |
Thermal units | 12.2kBTU/hr, 3.06 kcal/hr |
TS7770 Storage Expansion Frame power requirements
Your facility must ensure an available power supply to meet the input voltage requirements for the TS7770 Storage Expansion Frame. Table 7 displays the maximum input power for a fully configured TS7770.
Power requirement | Value |
---|---|
Voltage | 200-240 V AC (single phase) |
Frequency | 50-60 Hz (+/- 3 Hz) |
Current | 24 amp |
Leakage current | 13.5 ma |
Inrush current | 250 amp |
Power (watt) | 4400 watts |
Input power required | 4.8 kVA (single phase) |
Thermal units | 15.4 kBtu/hr, 4.0 kcal/hr |
Exhaust capacity | 1030 m3/hr |
Noise level | 59 db |