Power consumption and cooling requirements
The power and cooling requirements for a frame depend on the frame model type, feature codes, and number and type of tape drives installed. Generally, the greater the number of tape drives in a frame, the more heat the frame generates. The cooling requirements increase in direct proportion to the amount of heat that is generated.
Description | Power consumption (watts) | Cooling requirements
(Btu/hr, max. continuous) 2 |
||
---|---|---|---|---|
Off 1 | Idle | Max. continuous (not peak) |
||
FRAME MODELS | ||||
L25, L55 3, 4 | 11 | 95 | 130 | 443 |
D25, D55, S25, S55 3, 5 | 0 | 11 | 11 | 38 |
FEATURE CODES | ||||
FC 1442 HA kit with second accessor | 0 | 24 | 85 | 290 |
FC 1450 (TS4500 FCA) including one LCC and two AC/DC power supplies |
11 | 38 | 38 | 130 |
FC 1460 (redundant accessor power/network) | 0 | 5 | 5 | 17 |
FC 1521, 1522, 1523, 1524 (quad drive mounting kits) |
0 | 3 | 3 | 10 |
FC 1531, 1532, 1533, 1534 (quad drive mounting kits) |
0 | 3 | 3 | 10 |
FC 1751 PDU (for TR1 top rack) |
9 | 9 | 9 | 31 |
FC 1752 PDU | 17 | 17 | 17 | 58 |
FC 1951 PDU | 17 | 17 | 17 | 58 |
FC 1952 PDU | 34 | 34 | 34 | 116 |
TAPE DRIVES (3592) | ||||
TS1140 drive (3592 EH7) 6 | 0 | 28 | 50 | 171 |
TS1150 drive (3592 EH8) 6 | 0 | 23 | 48 | 164 |
TS1155 drive (3592 55F) 6 | 0 | 23 | 48 | 164 |
TS1155 drive (3592 55E) 6 | 0 | 50 | 63 | 215 |
TS1160 drive (3592 60F) 6 | 0 | 39 | 63 | 215 |
TS1160 drive (3592 60E) 6 | 0 | 38 | 62 | 211 |
TS1160 drive (3592 60S) 6 | 0 | 38 | 62 | 211 |
TAPE DRIVES (LTO) | ||||
LTO 5 drive (3588 F5C)6 | 0 | 16 | 32 | 109 |
LTO 6 drive (3588 F6C)6 | 0 | 13 | 36 | 123 |
LTO 7 drive (3588 F7C) 6 | 0 | 15 | 31 | 106 |
LTO 8 drive (3588 F8S and F8C)6 | 0 | 18 | 40 | 136 |
LTO 9 drive (3588 F9S, F9C, and S9C)6 | 0 | 18 | 37 | 126 |
Notes:
|
Frame model, feature codes, and drives | Quantity | Power (watts) | Cooling (kBtu/hr)1 | ||
---|---|---|---|---|---|
Off | Idle | Max. continuous | Max. continuous | ||
L25 | 1 | 11 | 95 | 130 | 0.4 |
FC 1460 (redundant accessor power/network) | 1 | 0 | 5 | 5 | 0.0 |
FC 1531, 1532, 1533, and 1534 (one of each FC per frame) | 4 | 0 | 12 | 12 | 0.0 |
TS1160 drives | 12 | 0 | 468 | 756 | 2.6 |
D25 | 3 | 0 | 33 | 33 | 0.1 |
FC 1450 (TS4500 FCA including one LCC and two ac/dc power supplies) | 3 | 33 | 114 | 114 | 0.4 |
FC 1531, 1532, 1533, and 1534 (one of each FC per frame) | 12 | 0 | 36 | 36 | 0.1 |
TS1160 drives | 48 | 0 | 1872 | 3024 | 10.3 |
S25 | 4 | 0 | 44 | 44 | 0.2 |
FC 1442 (HA kit with second accessor; for Dx5 or Sx5) | 1 | 0 | 24 | 85 | 0.3 |
Total library power consumption (watts) | -- | 44 | 2703 | 4239 | 14.5 |
Total cooling requirement (kBtu/hr)1 | -- | 0.2 | 9.2 | 14.5 | -- |