Power requirements for frames

A description of the power requirements for frames in the TS3500 tape library.

Table 1 lists the electrical characteristics for the TS3500 tape library frame models.

Table 1. Electrical characteristics of the TS3500 tape library frame models
Electrical characteristic Rating2
TS3500 tape library Models L22, D22, L32, D32, L52, D52
Nameplate electrical limits1 200–240 V ac, 8.0 A, 50–60 Hz, 1.6 kVA, single phase 100–127 V ac, 12.0 A, 50–60 Hz, 1.2 kVA, single phase
200–240 V ac, 8.0 A, 50–60 Hz, 1.6 kVA, single phase
Inrush current 150 A @ 200–240 V ac (peak for 1/2 cycle) 100 A @ 120 V ac, 200 A @ 240 V ac (peak for 1/2 cycle)
Leakage current 1 mA 8 mA maximum with 12 drive power supplies installed
Notes:
  1. Maximum certified electrical limits for a single frame. Nameplate limits should not be used to calculate product power or cooling requirements.
  2. Models HA1, SC1, S24, and S54 do not connect to external ac power.

Table 2 lists the power consumption of the TS3500 tape library models, power consuming features, and drive canisters.

Table 2. Power consumption of TS3500 tape library frame models, power consuming features, and drive canisters
Models Power consumption (Watts)
Off7 Idle Max. continuous (not peak)
L32, L22, L52 7 200 260
D32, D22, D522 7 200 200
L23, L531 13 142 202
D23, D531,2 13 103 103
S24, S543 0 5 5
HA14 0 24 85
SC1 (FC 1850 and 1851)8 0 11 20
Feature Codes
FC 1503 and 1504 (Drive mounting kit for xx2 models)5 0 15 20
FC 1513, 1514, and 1515
(Drive mounting kit for xx3 models)5
0 4 7
FC 1950 PDU 5 17 17
FC 4872
TS7700 backend 4 Gb switches (2x)
0 113 113
FC 4875
TS7700 backend 8 Gb switches (2x)
0 86 86
Tape drives6
TS1120 (3592 Models E05 and J1A) 0 27 42
TS1130 (3592 Model E06) 0 17 46
TS1140 (3592 Model E07) 0 23 50
TS1150 (3592 Model E08) 0 23 47
TS1155 (3592 Model 55G) 0 23 47
TS1160 (3592 Model 60G) 0 47 61
TS1030 (LTO 3588 F3B) 0 20 34
TS1040 (LTO 3588 F4A) 0 18 36
TS1050 (LTO 3588 F5A) 0 12 28
TS1060 (LTO 3588 F6A) 0 9 32
TS1070 (LTO 3588 F7A) 0 16 34
TS1080 (LTO 3588 F8A) 0 16 34
Notes:
  1. These models come equipped with dual ac line cords. The figures in this table show the total power consumed, including power consumed by redundant power supplies. Each individual line cord supplies approximately half of the power.
  2. Frames with no frame control assembly (FCA) or enhanced FCA consume no power and require no cooling.
  3. S-frame power is for internal lighting and is provided by the power supplies in frames that are equipped with power.
  4. The HA1 frame is not connected to ac power. The power shown is the total consumed by the second accessor and is provided by the power supplies in frames that are equipped with power.
  5. Drive mounting kit power includes ac/dc conversion losses in drive power supplies (including redundant power), but does not include power consumed by the drive canister.
  6. Drive power includes the drive and canister cooling fan, but does not include power losses in external ac or dc drive power supplies. Idle power is consumed when the drive has no tape cartridge loaded. Maximum continuous power is consumed when the drive is actively writing to a tape cartridge.
  7. "Off" refers to power consumed when the library is connected to an ac power source and the library on/off switch is set to off.
  8. Model SC1 power is provided by the library frames to which it connects. The idle power is the power consumed by each shuttle station when no shuttle car is present. The maximum continuous power is the power consumed by the shuttle station when the shuttle car is present.

In order to calculate the total power consumption (in watts) of a particular library configuration, multiply the quantity of each power consuming item in the configuration by the corresponding value in Table 2 and calculate the total. In order to calculate the total cooling required by the library (in Btu/hr), multiply the total power in watts by 3.4. To convert Btu/hr to kBtu/hr, divide your result by 1000.

Table 3 provides a sample calculation of total power and cooling requirements for a TS3500 tape library configuration consisting of one L23 with ten TS1130 tape drives and mounting kits, four D23 models each containing six TS1130 tape drives and mounting kits, one D23 with no drives or enhanced FCA feature (FC 1451), two S24 models, and one HA1 model.

Table 3. Sample calculation of total library power consumption and cooling requirements.
This model With this feature code And these tape drives Quantity Power (Watts)
Off Idle Max. continuous
L23 15151 TS1130 1 13 142 202
10 0 40 70
10 0 170 460
D23
(with FC 14512)
1515 TS1130 4 52 412 412
24 0 96 168
24 0 408 1104
D23
(without FC 1451)
N/A N/A 1 0 0 0
S24 N/A N/A 2 0 10 10
HA1 N/A N/A 1 0 24 85
Total power consumption: 65 1302 2511
Total cooling requirement (kBtu/hr): 0.2 4.4 8.5
Notes:
  1. FC 1515: Tape drive mounting kit for L23 and D23 frames.
  2. FC 1451: Enhanced frame control assembly for D23 and D53 frames.

Library power consumption is dynamic and usage dependent. Short peaks might exceed the maximum continuous power values. Typical average power consumption is lower than the calculated maximum continuous value because all drives are not likely to be active simultaneously.