7042-CR9 Hardware Management Console specifications
Hardware specifications for model 7042-CR9 provide detailed information for your Hardware Management Console (HMC), including dimensions, electrical, power, temperature, environmental specifications, and noise emissions.
The HMC controls managed systems, including the management of logical partitions and the use of capacity on demand. Using service applications, the HMC communicates with managed systems to detect, consolidate, and send information to IBM® for analysis. The HMC provides service technicians with diagnostic information for systems that can operate in a multiple-partitioned environment.
Use the following specifications to plan for your HMC.
Width | Depth | Height | Weight |
---|---|---|---|
429 mm (16.9 in.) | 734 mm (28.9 in.) | 43.0 mm (1.7 in.) | 15.9 kg (35 lb) |
Electrical characteristics | Properties |
---|---|
Minimum measured power | 135 W |
Maximum measured power | 183 W |
Minimum kVA | 0.14 |
Maximum kVA | 0.191 |
Minimum thermal output | 460.62 BTU/hr |
Maximum thermal output | 624.4 BTU/hr |
Input voltage (low range) | 100 - 127 V ac |
Input voltage (high range) | 200 - 240 V ac |
Frequency | 50 or 60 Hz |
|
Environment | Allowable operating | Nonoperating (system off) | Nonoperating (storage) | Nonoperating (shipping) |
---|---|---|---|---|
ASHRAE class | A3 | |||
Airflow direction | Front-to-back | |||
Temperature | 5°C - 40°C (41°F - 104°F) at 0 - 950 m (0 - 3117 ft) Decrease maximum system temperature by 1°C for every 175 m (574 ft) above 950 m (3117 ft). 5°C - 28°C (41°F - 82°F) at 3050 m (10000 ft) |
5°C - 45°C (41°F - 113°F) | 1°C - 60°C (33.8°F - 140.0°F) | -40°C to 60°C (-40°F to 140°F) |
Humidity range | Non-condensing: -12.0°C (10.4°F) dew point Relative humidity (RH): 8% - 85% |
8% - 85% RH | 5% to 80% RH | 5% - 100% RH |
Maximum dew point | 24°C (75°F) | 27°C (80.6°F) | 29°C (84.2°F) | 29°C (84.2°F) |
Maximum altitude | 3050 m (10000 ft) | 3050 m (10000 ft) | 3050 m (10000 ft) | 10700 m (35105 ft) |
Acoustical characteristics | Idling | Operating |
---|---|---|
LWAd | 6.1 bels | 6.1 bels |
|