Use the Floor loading for system tables to determine the floor loading for various configurations.
| Floor loading for system with 8 I/O drawers and without integrated battery backup | |||||||
| a (sides) | b (front) | c (back) | 1 frame | ||||
| mm | in. | mm | in. | mm | in. | lb/ft2 | kg/m2 |
| 25 | 1.0 | 254 | 10.0 | 254 | 10.0 | 208.9 | 1020.2 |
| 25 | 1.0 | 508 | 20.0 | 508 | 20.0 | 166.3 | 811.8 |
| 25 | 1.0 | 762 | 30.0 | 762 | 30.0 | 139.7 | 681.9 |
| 254 | 10.0 | 254 | 10.0 | 254 | 10.0 | 142.1 | 693.6 |
| 254 | 10.0 | 508 | 20.0 | 508 | 20.0 | 114.9 | 561.0 |
| 254 | 10.0 | 762 | 30.0 | 762 | 30.0 | 98.0 | 478.3 |
| 508 | 20.0 | 254 | 10.0 | 254 | 10.0 | 108.4 | 529.1 |
| 508 | 20.0 | 508 | 20.0 | 508 | 20.0 | 89.0 | 434.7 |
| 508 | 20.0 | 762 | 30.0 | 762 | 30.0 | 77.0 | 375.8 |
| 762 | 30.0 | 254 | 10.0 | 254 | 10.0 | 89.7 | 438.2 |
| 762 | 30.0 | 508 | 20.0 | 508 | 20.0 | 74.7 | 364.8 |
| 762 | 30.0 | 762 | 30.0 | 762 | 30.0 | 65.4 | 319.1 |
| Note:
|
|||||||
| Floor loading for systems with 6 I/O drawers and with integrated battery backup | |||||||
| a (sides) | b (front) | c (back) | 1 frame | ||||
| mm | in. | mm | in. | mm | in. | lb/ft2 | kg/m2 |
| 25 | 1.0 | 254 | 10.0 | 254 | 10.0 | 189.0 | 922.9 |
| 25 | 1.0 | 508 | 20.0 | 508 | 20.0 | 151.0 | 737.1 |
| 25 | 1.0 | 762 | 30.0 | 762 | 30.0 | 127.2 | 621.2 |
| 254 | 10.0 | 254 | 10.0 | 254 | 10.0 | 129.4 | 631.7 |
| 254 | 10.0 | 508 | 20.0 | 508 | 20.0 | 105.2 | 513.4 |
| 254 | 10.0 | 762 | 30.0 | 762 | 30.0 | 90.1 | 439.7 |
| 508 | 20.0 | 254 | 10.0 | 254 | 10.0 | 99.3 | 485.0 |
| 508 | 20.0 | 508 | 20.0 | 508 | 20.0 | 82.1 | 400.8 |
| 508 | 20.0 | 762 | 30.0 | 762 | 30.0 | 71.3 | 348.3 |
| 762 | 30.0 | 254 | 10.0 | 254 | 10.0 | 82.7 | 403.9 |
| 762 | 30.0 | 508 | 20.0 | 508 | 20.0 | 69.3 | 338.5 |
| 762 | 30.0 | 762 | 30.0 | 762 | 30.0 | 61.0 | 297.8 |
| Note:
|
|||||||
| Floor loading for system with 12 I/O drawers and without integrated battery backup | |||||||
| a (sides) | b (front) | c (back) | 2 frames | ||||
| mm | in. | mm | in. | mm | in. | lb/ft2 | kg/m2 |
| 25 | 1.0 | 254 | 10.0 | 254 | 10.0 | 167.5 | 817.7 |
| 25 | 1.0 | 508 | 20.0 | 508 | 20.0 | 134.4 | 656.3 |
| 25 | 1.0 | 762 | 30.0 | 762 | 30.0 | 113.8 | 555.7 |
| 254 | 10.0 | 254 | 10.0 | 254 | 10.0 | 135.5 | 661.6 |
| 254 | 10.0 | 508 | 20.0 | 508 | 20.0 | 109.9 | 536.4 |
| 254 | 10.0 | 762 | 30.0 | 762 | 30.0 | 93.9 | 458.4 |
| 508 | 20.0 | 254 | 10.0 | 254 | 10.0 | 113.4 | 553.9 |
| 508 | 20.0 | 508 | 20.0 | 508 | 20.0 | 92.9 | 453.7 |
| 508 | 20.0 | 762 | 30.0 | 762 | 30.0 | 80.1 | 391.3 |
| 762 | 30.0 | 254 | 10.0 | 254 | 10.0 | 98.7 | 482.1 |
| 762 | 30.0 | 508 | 20.0 | 508 | 20.0 | 81.6 | 398.5 |
| 762 | 30.0 | 762 | 30.0 | 762 | 30.0 | 71.0 | 346.5 |
Note:
|
|||||||
| Floor loading for system with 12 I/O drawers and with integrated battery backup | |||||||
| a (sides) | b (front) | c (back) | 2 frames | ||||
| mm | in. | mm | in. | mm | in. | lb/ft2 | kg/m2 |
| 25 | 1.0 | 254 | 10.0 | 254 | 10.0 | 181.3 | 885.3 |
| 25 | 1.0 | 508 | 20.0 | 508 | 20.0 | 145.1 | 708.3 |
| 25 | 1.0 | 762 | 30.0 | 762 | 30.0 | 122.4 | 597.9 |
| 254 | 10.0 | 254 | 10.0 | 254 | 10.0 | 146.2 | 714.0 |
| 254 | 10.0 | 508 | 20.0 | 508 | 20.0 | 118.1 | 576.7 |
| 254 | 10.0 | 762 | 30.0 | 762 | 30.0 | 100.6 | 491.1 |
| 508 | 20.0 | 254 | 10.0 | 254 | 10.0 | 122.0 | 595.9 |
| 508 | 20.0 | 508 | 20.0 | 508 | 20.0 | 99.5 | 485.9 |
| 508 | 20.0 | 762 | 30.0 | 762 | 30.0 | 85.5 | 417.4 |
| 762 | 30.0 | 254 | 10.0 | 254 | 10.0 | 105.9 | 517.0 |
| 762 | 30.0 | 508 | 20.0 | 508 | 20.0 | 87.1 | 425.4 |
| 762 | 30.0 | 762 | 30.0 | 762 | 30.0 | 75.4 | 368.3 |
| Note:
|
|||||||