Model 7965-S42 rack specifications

Hardware specifications provide detailed information for your rack, including dimensions, electrical, power, temperature, environment, and service clearances.

Table 1. Dimensions for rack
  Width Depth Height Weight (Empty) EIA unit capacity
Rack only 600 mm (23.6 in.) 1070 mm (42.1 in.) 2020 mm (79.5 in.) 166 kg (365 lb) 42 EIA units
Rack with two standard doors 600 mm (23.6 in.) 1132 mm (44.6 in.) 2020 mm (79.5 in.) 177 kg (391 lb) 42 EIA units
Rack with rear door heat exchanger (dry) and standard doors 600 mm (23.6 in.) 1231 mm (48.5 in.) 2020 mm (79.5 in.) 210 kg (463 lb) 42 EIA units
Rack with high-end appearance front door and rear door 600 mm (23.6 in.) 1201 mm (47.3 in.) 2020 mm (79.5 in.) 181 kg (398 lb) 42 EIA units
Table 2. Weight capacity limits
Characteristics Maximum weight EIA unit capacity
Dynamic (rolling) 1134 kg (2500 lb) 18 kg (40 lb) / EIA average
Static 1678 kg (3700 lb) 32 kg (70 lb) / EIA average
Seismic certified 1170 (2580 lb) 20 kg (45 lb) / EIA maximum
Table 3. Dimensions for doors
Door model Width Height Depth Weight

Standard front door and standard back door

590 mm (23.2 in.) 1942 mm (76.5 in.) 31 mm (1.2 in.) 5.9 kg (13 lb)
Rear door heat exchanger door 600 mm (23.6 in.) 1950 mm (76.8 in.) 129 mm (5.0 in.) 39 kg (85 lb) - empty
48 kg (105 lb) - filled
High-end appearance front door, panels 590 mm (23.2 in.) 1942 mm (76.5 in.) 81 mm (3.0 in.) 12.3 kg (27 lb)
High-end appearance front door, chevrons 590 mm (23.2 in.) 1942 mm (76.5 in.) 100 mm (3.9 in.) 9.1 kg (20 lb)

FC ECRC and ECRD acoustic front and rear doors, black IBM®

590 mm (23.2 in.)

1942 mm (76.5 in.)

115.5 mm (4.6 in)

17.7 kg (39 lb)

FC ECRC and ECRD acoustic front and rear doors, black OEM

590 mm (23.2 in.)

1942 mm (76.5 in.)

110 mm (4.3 in)

17.7 kg (39 lb)

Table 4. Dimensions for side covers
Width1 Depth Height Weight2
12 mm (0.5 in.) 1070 mm (42.1 in.) 1942 mm (76.5 in.) 20 kg (44 lb)

1 Side covers increase the overall width of the rack by 12 mm (0.5 in.) per side, but are only used on the ends of the rows.

2 Weight is for each side cover.

Table 5. Environment requirements1
Environment Recommended operating Allowable operating Nonoperating
ASHRAE class   A3  
Airflow direction   Front-to-back  
Temperature2 18°C - 27°C (64°F - 80°F) 5°C - 40°C (41°F - 104°F) 1°C - 60°C (34°F - 140°F)
Humidity range 5.5°C (42°F) dew point (DP) to 60% relative humidity (RH) and 15°C (59°F) dew point -12.0°C (10.4°F) DP and 8% - 80% RH 8% - 80% RH
Maximum dew point   24°C (75°F) 27°C (80°F) 
Maximum operating altitude   3050 m (10000 ft)  
Shipping temperature     -40°C to 60°C (-40°F to 140°F)
Shipping relative humidity     5% - 100%
  1. The final ASHRAE class is determined by the hardware that is installed in the rack. Individual specifications for each piece of hardware must be reviewed.
  2. Derate maximum allowable dry-bulb temperature 1°C per 175 m above 950 m. IBM recommends a temperature range of 18°C - 27°C (64°F - 80.6°F).
Table 6. Service clearances
Front1 Back
915 mm (36 in.) 915 mm (36 in.)
1 Storage racks require larger service clearances in the front of the rack.

Rear door heat exchanger

Specifications for Power orderable feature code (FC) EC05 (Rear door heat exchanger indicator (Model 1164-95X)).

Table 7. Dimensions for rear door heat exchanger
Width Depth Height Weight (empty) Weight (filled)
600 mm (23.6 in.) 129 mm (5.0 in.) 1950 mm (76.8 in.) 39 kg (85 lb) 48 kg (105 lb)

For more information, see Model 1164-95X rear door heat exchanger specifications.

Electrical

For electrical requirements, see Power distribution unit and power cord options.

Floor cutout

Racks with water hoses and power cords that exit from the bottom of the rack require a floor tile cutout of at least 30.48 cm (12 in.) long by 22.86 cm (9 in.) wide. Due to the hose bend radii, the hole must be positioned towards the side of the rack without the manifold (the left side of the rack when looking at the rear of the rack). The left edge of the hole must be at least 11.43 cm (4.5 in.) from the side and 3.81 cm (1.5 in.) from the back edge of the rack (not including doors). Hole placement on the tile depends on the location of the rack, tile size, and tile load limitations.

Figure 1. Floor cutout
Floor cutout

Caster and leveler locations

The following diagram provides the caster and leveler locations for the 7965-S42 rack.

Figure 2. Caster and leveler locations