If you plan to install front or back ac electrical outlets
in the rack, the rack must be bolted to the floor. When you attach
the rack to a concrete floor, which lays beneath a raised floor, follow
the procedure described in this section.
Obtain the services of a mechanical contractor to attach
the rack-mounting plates to the concrete floor. The mechanical contractor
needs to determine that the hardware being used to secure the rack-mounting
plates to the concrete floor is sufficient to meet the requirements
for the installation.
To attach the rack to a concrete floor
beneath a raised floor, complete the following steps:
- Put your rack in its predetermined location and tighten
the locking screws on the casters.
- If installed, remove the top, left and right trim panels.
The trim panels are held in place with spring clips. See the following
illustration.
| 1 |
Rack chassis |
4 |
Right-side trim panel |
| 2 |
Top trim panel |
5 |
Spring clip |
| 3 |
Left-side trim panel |
|
|
Figure 1. Removing the trim panels
- If installed, remove the front and rear doors. For instructions,
see Attaching the rack doors.
After the rack doors have been removed, go to the next step.
- Locate the hardware mounting kit and the two mounting plates.
Refer to the following illustration when reviewing the contents of
the hardware mounting kit. The hardware mounting kit contains the
following items:
- Four rack-mounting bolts
- Four thin washers
- Eight plastic isolator bushings
- Four thick washers
- Four spacers
- If you are installing an ac-powered rack, temporarily
install the lower plastic isolator bushings to help you locate the
rack-mounting plate. After the mounting plate has been correctly located,
remove the lower plastic isolator bushings.
Figure 2. Installing
the ac power-mounting plates
| 1 |
Rack chassis |
7 |
Jam nut |
| 2 |
Rack-mounting bolt |
8 |
Leveling foot |
| 3 |
Thin washer |
9 |
Lower plastic isolator bushing (used only
on dc powered systems) |
| 4 |
Top plastic isolator bushing |
ac |
Typical leveling foot installation for an
ac-powered rack |
| 5 |
Thick washer |
dc |
Typical leveling foot installation for an
dc-powered rack |
| 6 |
Spacer |
|
|
- Position the two mounting plates in the approximate mounting
location under the rack.
- Create a rack-mounting bolt assembly by adding the following
items, in the order listed, to each rack-mounting bolt.
- Thin washer
- Top plastic isolator bushing
- Thick flat washer
- Spacer
- Insert a rack-mounting bolt assembly through each of the
leveling feet.
- Reposition the rack-mounting plates under the four rack-mounting
bolts so that the mounting bolts are centered directly over the threaded
bolt holes.
- Turn the rack-mounting bolts four complete turns into the
mounting plate's threaded bolt holes.
- Mark the raised-floor panel around the edges of front and
rear rack-mounting plates.
- Mark the plate bolt-down holes that are accessible through
the opening in the rear of the rack.
- Remove the rack-mounting bolt assemblies.
- If you are installing an ac-powered rack, remove the bottom
isolator bushing from each of the leveling feet.
- Remove the rack-mounting plates from the marked locations.
- Loosen each of the locking screws on the casters.
- Move the rack so that it is clear of both areas that were
marked on the floor for the rack-mounting plate locations.
- Reposition the mounting plates within the marked areas.
- Mark the raised-floor panel at the center of each hole
in the rack-mounting plates (including the tapped holes).
- Remove the two rack-mounting plates from the marked locations
on the raised floor panel.
- Drill two clearance holes on each end of each rack-mounting
plate. The drilled holes should be approximately 1-inch deep. This
depth will accommodate any rack-mounting bolt extending past the rack-mounting
plate when securing the rack to the rack-mounting plate.
- For each rack-mounting plate, select at least two suitable
hole locations. Select the hole locations as close to the threaded
hole areas as possible. Be sure the hole locations selected at the
back of the rack are accessible.
- Drill pass-through holes in the raised-floor panel. The
pass-through holes allow the anchor bolts to be inserted into the
rack-mounting plate and pass through the raised floor panel to the
concrete floor.
Note: You must use a minimum of
two anchor bolts for each rack-mounting plate to securely attach the
rack-mounting plate through the raised-floor panel to the concrete
floor. Because some of the holes in each rack-mounting plate may align
with concrete reinforcement rods imbedded in the concrete, some of
the rack-mounting plate holes might not be usable.
- Transfer the locations of the anchor bolt holes (exclude
the clearance holes drilled for the rack-mounting bolts) from the
raised-floor panel to the concrete floor directly beneath, and mark
the hole locations on the concrete floor.
- Drill holes in the concrete floor to secure the anchor
bolts.
- Position the raised-floor panel back into position over
the anchor bolt holes.
- Position the front stabilizer bracket within the marked
area on the raised-floor panel.
- Using your anchor bolts, secure the front stabilizer brackets
on top of the raised floor and through to the concrete floor.
- Position the rear stabilizer brackets within the marked
area on the raised-floor panel.
| 1 |
Rack-mounting bolt |
7 |
Leveling foot |
| 2 |
Thin washer |
8 |
Lower plastic isolator bushing (used only
on dc-powered systems) |
| 3 |
Top plastic isolator bushing |
9 |
Stabilizer brackets |
| 4 |
Thick washer |
10 |
Threaded hole (used to secure the rack to
mounting plate.) |
| 5 |
Spacer |
11 |
Anchor bolt hole |
| 6 |
Jam nut |
12 |
Traced pattern (pattern to be traced onto
the floor using the mounting plate as a template) |
Figure 3. Securing the rack to the floor
- Using your anchor bolts, secure the back stabilizer bracket
on top of the raised floor and through to the concrete floor.
- Replace all raised-floor panels that may have been removed
when aligning and securing the anchor bolts to the concrete floor.
- Align the rack over the front and rear stabilizer brackets.
- Insert each of the bolt assemblies through a leveling foot.
- Align the rack-mounting bolts with the threaded holes in
each stabilizer bracket. Turn each bolt three to four rotations.
- Tighten the locking screw on each caster.
- Adjust the leveling feet downward as needed until the rack
is level. When the rack is level, tighten the jam nuts against the
base of the rack.
- If you have multiple racks that are connected as a suite
(bolted to each other), go to Connecting multiple racks with rack-to-rack attachment kit. Otherwise, torque
the four bolts to 54 - 67 newton-meters (40 - 50 foot-pounds).
- If you are not installing doors on your rack, install the
top, left, and right trim panel.
- Connect the power distribution system. For instructions,
see Connecting the power distribution system.
- After the rack is bolted down and you are going to attach
a front electrical outlet, go to Attaching the front or back ac electrical outlet.
- If you are not going to attach a front electrical outlet
and you are installing rack doors, go to Attaching the rack doors.