The system detected a warning or fault due to the ambient
room temperature.
- Is the room temperature less than 35°C (95°F)?
- No: Notify the customer. The customer must bring the room
temperature within normal range. Continue with the next step.
- Yes: Continue with the next step.
- Are the system front and rear doors free of obstructions?
- No: Notify the customer. The system must be free of obstructions
for proper air flow. Continue with the next step.
- Yes: Continue with the next step.
- If applicable, do all the positions in the processor subsystem
contain processors or fillers?
- Yes: Continue with the next step.
- No: Fill any open positions with processors or fillers.
This ends the procedure.
- Do all the power supply positions contain power supplies or fillers?
- Yes: Continue with the next step.
- No: Fill any open positions with supplies or fan books.
This ends the procedure.
- Are you working with reference code 7201?
- Yes: This indicates that the room temperature is too high.
The customer must bring the room temperature to less than 35°C (95°F).
If the room temperature is less than 35°C (95°F), continue with the
next step. This ends the procedure.
- No: Continue with the next step.
- Perform one of the following options:
- For model 8203-E4A, 8261-E4S, 9407-M15, or 9408-M25: Replace
the control panel. Use the following table to determine the part number
for the field replaceable unit (FRU). Then continue with the next
step.
| CCIN or FFC |
Type and model |
Part number |
Description |
Location code |
| |
8203-E4A, 8261-E4S, 9407-M15, 9408-M25 |
10N9737 |
Control (operator) panel |
Un-D1 |
- For model 8204-E8A or 9409-M50: Replace the control panel.
Use the following table to determine the part number for the field
replaceable unit (FRU). Then continue with the next step.
| CCIN or FFC |
Type and model |
Part number |
Description |
Location code |
| |
8204-E8A, 9409-M50 |
42R5505 |
Control (operator) panel |
Un-D1 |
- For model 8234-EMA, 9406-MMA or 9117-MMA: Replace the
regulator distribution connection backplane. Use the following table
to determine the part number for the field replaceable unit (FRU).
Then continue with the next step.
- For the 5802 expansion unit: Replace the power supply
at location Un-E1. If this does not resolve the
problem, replace the power supply at location Un-E2.
Use the following table to determine the part number for the field
replaceable unit (FRU). Then continue with the next step.
- After each FRU is replaced, is the error code that sent you to
this procedure still reported?
- No: The problem has been corrected. This ends the procedure.
- Yes: Replace the next FRU on the list. If all FRUs on
the list have been replaced, call your next level of support. This
ends the procedure.