Model 7953-94X and 7965-94Y rack

Hardware specifications provide detailed information for your rack, including dimensions, electrical, power, temperature, environment, and service clearances.

Table 1. Dimensions for rack
  Width Depth Height Weight (Empty) Weight (Maximum configuration) EIA unit capacity
Rack only 600 mm (23.6 in.) 1095 mm (43.1 in.) 2002 mm (78.8 in.) 130 kg (287 lb) 1140 kg (2512 lb) 42 EIA units
Rack with standard doors 600 mm (23.6 in.) 1145.5 mm (45. in.) 2002 mm (78.8 in.) 138 kg (304 lb) N/A N/A
Rack with triplex doors 600 mm (23.6 in.) 1206.2 - 1228.8 mm (47.5 - 48.4 in.) 2002 mm (78.8 in.) 147 kg (324 lb) N/A N/A
Rack with rear door heat exchanger indicator 600 mm (23.6 in.) 1224 mm (48.2 in.) 2002 mm (78.8 in.) 169 kg (373 lb) N/A N/A
Note: When the rack is delivered or is moved, outriggers are needed for stability. For more information about outriggers, see Side stabilizing outriggers.
Table 2. Dimensions for doors
Door model Width Height Depth Weight

Standard front door (FC EC01)

and

standard back door (FC EC02)

597 mm (23.5 in.) 1925 mm (75.8 in.) 22.5 mm (0.9 in.) 7.7 kg (17 lb)
Triplex door (FC EU21)3 597.1 mm (23.5 in.) 1923.6 mm (75.7 in.) 105.7 mm (4.2 in.)1 16.8 kg (37 lb)
128.3 mm (5.2 in.)2

1 Measured from the front flat surface of the door.

2 Measured from the IBM® logo on the front of the door.

3 Multiple racks that are placed side-by-side must have a 6 mm (0.24 in.) minimum clearance between racks to allow the triplex front door to hinge properly. Feature code EC04 (Rack suite attachment kit) can be used to maintain the 6 mm (0.24 in.) minimum clearance between racks.

Table 3. Dimensions for side covers1
Depth Height Weight
885 mm (34.9 in.) 1870 mm (73.6 in.) 17.7 kg (39 lb)
1 Side covers do not increase the overall width of the rack.
Table 4. Temperature requirements
Operating Nonoperating
10°C - 38°C (50°F - 100.4°F)1 -40°C to 60°C (-40°F to 140°F)
1 The maximum 38°C (100.4°F) temperature must be derated 1°C (1.8 °F) per 137 m (450 ft) above 1295 m (4250 ft).
Table 5. Environmental requirements
Environment Operating Nonoperating Maximum altitude
Noncondensing humidity 20% - 80% (allowable)

40% - 55% (recommended)

8% - 80% (including condensing) 2134 m (7000 ft) above sea level
Wet bulb temperature 21°C (69.8°F) 27°C (80.6°F)
Table 6. Service clearances
Front Back Side1
915 mm (36 in.) 915 mm (36 in.) 610 mm (24 in.)
1 Side service clearance is only required when outriggers are on the rack. Side service clearance is not required during normal operation of the rack when outriggers are not installed.

Rear door heat exchanger

Specifications for Power orderable feature code (FC): EC05 - Rear door heat exchanger indicator (Model 1164-95X).

Table 7. Dimensions for rear door heat exchanger
Width Depth Height Weight (empty) Weight (filled)
600 mm (23.6 in.) 129 mm (5.0 in.) 1950 mm (76.8 in.) 39 kg (85 lb) 48 kg (105 lb)

For more information, see Model 1164-95X rear door heat exchanger.

Electrical

For electrical requirements, see Power distribution unit and power cord options.

Features

The 7953-94X and 7965-94Y rack has the following features available for use:

  • Recirculation prevention plate that is installed at the bottom, front of the rack.
  • Stabilizer bracket that is installed at the front of the rack.

Caster locations

The following diagram provides the caster locations for the 7953-94X and 7965-94Y rack.

Figure 1. Caster locations Caster locations